2006-08-03 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 TRUSS PACKAGE:
 1- ENGINEER TO PROVIDE ALL HIS
 INFORMATION IN ALL DWGS AS REQ'D BY
 CHAPTER 471 FL. ST. & SEC. 61G15-23.002
 OF FLORIDA ADMINISTRATIVE CODE.
  
 2- ALL ENGINEER DRAWINGS AND LETTERS
 NEED TO BE SIGNED AND SEALED AS REQUIRED
 BY CHAPTER 471 FL. ST. AND 61G15-23.002,
 INCLUDING ALL GENERAL NOTES AND GENERAL
 DETAILS.
  
 3- A) GENERAL DETAILS NEED TO BE
 UPDATED. FBC 2004 CALLS FOR ASCE 7-02,
 NOT ASCE 7-98. ENGINEER TO UPDATE ALL
 DRAWINGS.
 B) PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB. PLEASE, DON'T PROVIDE
 UNNECESSARY INFORMATION TO EXPEDITE THE
 REVIEW PROCESS.
  
 4- DESIGN LOADS SHOWN IN TRUSS LAYOUT,
 ENGINEERED TRUSS AND GENERAL DRAWINGS
 NEED TO MATCH. REVISE AS REQUIRED.
  
 5- SPECIFY ROOF SHEATHING NAILING. SEE
 TABLE 2304.9.1 FBC 2004.
  
 6- SPECIFY TRUSS TO WALL CONNECTORS AND
 PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72. GO
 TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 PRODUCT APPROVALS.
  
 7- ROOF PITH OF 2.5:12 REQUIRES 2 LAYERS
 OF UNDERLAYMENT. SEC. 1507.2.2 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER