2006-07-11 00:00:00BUILDING REVIEW CHECKLIST:
 1- 5-V CRIMP METAL ROOFING PANEL SYSTEM
 (NOA #01-0919.11) IS LIMITED TO A
 MAXIMUM UPLIFT PRESSURE OF -57.5PSF.
 ACCORDING TO TABLE 1609.6B FBC 2004
 SYSTEM NEEDS TO RESIST DESIGN PRESSURES
 OF -68.1PSF AT PERIMETER AND CORNER
 AREAS.SYSTEM LIMITATION NUMBER 1 ON
 PAGE 5 OF 5 OF NOA SUBMITTED ALLOWS
 INCREASED DESIGN PRESSURES AT PERIMETER
 AND CORNER AREAS. CALCULATIONS MUST BE
 DONE AND SIGNED AND SEALED BY ONE OF THE
 PROFESSIONALS LISTED IN LIMITATION #1.
 PROVIDE SUCH CALCULATIONS.
  
 2- PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND CURRENT DADE COUNTY NOA
 THAT WAS SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. SEE ATTACHED COPY OF CITY
 POLICY FOR RE-ROOFING PERMITS. GO TO
 WWW.FLORIDABUILDING.ORG AND LOOK FOR
 FL-986 TO DOWNLOAD EXACT DADE COUNTY NOA
 THAT WAS SUBMITTED FOR APPROVAL.
  
 3- VALUATION DECLARED IN THE PERMIT
 APPLICATION WAS UPDATED. OWES $43.63.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  