2006-12-07 08:41:09 | DENIED 4TH TIME |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS |
| PLAN REVIEW FROMPERVIOUS GAS PLAN REVIEW COMMENTS |
| DATED 7/26/06, 9/12/06 AND11/06/06. |
| A PERMIT FOR THE GENERATOR CAN NOT BE ISSUED UNTIL THE |
| FOLLOWING CORRECTIONS ARE MADE TO MEET CODE |
| COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE |
| MEASUREMENTS OF THE UNDERGROUND PE PIPING. RECORDS |
| INDICATE EXISTING GAS AT SAID ADDRESS PLEASE INDICATE |
| THE EXISTING GAS ON RESUBMITTED DRAWING.PLEASE |
| REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING |
| GAS AT SAID ADDRESS. PLEASE INDICATE THE CUT SECTION |
| MEASUREMENTS OF ALL PIPING, UNDERGROUND, ABOVE GROUND |
| AND EXISTING. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE |
| UNDERGROUND PIPING MATERIAL AND SIZE. WHAT IS THE SIZE |
| AND MATERIAL TYPE OF THE ABOVE GROUND AND EXISTING |
| PIPING. |
| |
| 3. (OK) |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: RECORDS INDICATE EXISTING GAS TO A 40 GAL. NAT. |
| GAS WATER HEATER. THE BTU LOAD TO THAT WATER HEATER |
| MUST BE INDICATED ON THE DRAWING. THE BTU LOAD OF |
| 343,000 INDICATED FOR THE GENERATOR ON THE RESUBMITTED |
| GAS ISOMETRIC IS STILL WRONG. THE CORRECT BTU LOAD IS |
| 437,000 PER THE SUBMITTED GENERATOR MANUFACTURE CUT |
| SHEETS. PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THE EXISTING GAS SYSTEM NEEDS TO BE INDICATED ON |
| THE RESUBMITTED DRAWINGS WITH ITS MEASUREMENTS. |
| |
| 6. (OK) |
| |
| 7. (OK) |
| |
| 8. (OK) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |