2006-11-06 13:46:03UNSAT (3RD TIME)
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE
 MEASURMENTS OF THE UNDERGROUND PE PIPING. WHAT ARE THE
 CUT SECTION MEASUREMENTS OF THE ABOVE GROUND PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATE THE
 UNDERGROUND PIPING MATERIAL AND SIZE. WHAT IS THE SIZE
 AND MATERIAL TYPE OF THE ABOVE GROUND PIPING?
  
 3. (OK)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: RECORDS INDICATE EXISTING GAS TO A 40 GAL. NAT.
 GASWATER HEATER, THE BTU LOAD TO THAT WATER HEATER
 MUST BE INDICATED ON THE DRAWING. THE BTU LOAD 343,000
 THAT IS INDICATED FOR THE GENERATOR IS WRONG ON THE
 RESUBMITTED ISOMETRIC, THE CORRECT BTU LOAD IS 437,000
 PER THE SUBMITTED GENERATOR MANUFACTURER SHEETS. PLEASE
 CORRECT THE BTU LOAD ON THE RESUBMITTAL.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE EXISTING GAS SYSTEM NEEDS TO BE INDICATED ON
 THE DRAING WITH ITS MEASUREMENTS.
  
 6. (OK)
  
 7. (OK)
  
 8. (OK)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  