2006-11-01 16:37:21 | ** UNSAT 3RD REVIEW ** |
| |
| ** PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN REVISED |
| WHICH HAS CREATED SOME NEW COMMENTS. |
| |
| 1) NOTE: PLEASE SEE RISER IS NOW SHOWING AND "EQUIPMENT |
| GROUNDING CONDUCTOR" FROM THE METER TO THE FIRST MEANS |
| OF DISCONNECT WHICH IS NOT PERMITTED. |
| PLEASE SEE 250.6, 250.24B. |
| |
| 2) NOTE: PLEASE SEE NOW A NEW GROUNDING ELECTRODE POINT |
| IS BEING SHOWN, HOWEVER NOW SIZE OF GEC OR SYSTEM |
| REQUIRED PER 250.50 IS BEING SHOWN>??? |
| |
| 3) NOTE: PLEASE SEE RISER SHOWS WHAT IS TO BE A "RTSE" |
| , PLEASE SUBMIT THE CORRESPONDING MANUFACTURES SPEC/CUT |
| SHEET FOR THE RTSE. |
| |
| 4) NOTE: PLEASE BE SURE ALL SHEETS CONTAIN THE PRINTED |
| NAME AND SIGNATUREOF THE PERSON RESPONSIBLE FOR |
| DESIGN/PLANS ETC. (PLEASE SEE LOAD CALCULATIONS). |
| FBC 106.1.2 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |