Plan Review Notes
Plan Review Notes For Permit 06070435
Permit Number 06070435
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-11 00:00:00*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO REVISED RISER BEING SUBMITTED
 NEED TO BE ADDRESSED. PLEASE SEE NOTES
 BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW WITH NEW NOTES ADDED BELOW.
  
 1) NOTE: NO, PLEASE SEERISER DOES NOT
 INDICATE WHERE THIS FEED IS GOING AFTER
 THE ATS?
 PLEASE SEE NO OVER VIEW WAS SUBMITTED
 SHOWING THE LOCATION OF ALL THE SERVICE
 EQUIPMENT.
 PLEASE SEE THE ATS AS SUBMITTED AND
 SHOWN ON RISER DOES NOT CONTAIN THE
 REQUIRED DISONNECTING MEANS FOR THE
 FEEDERS COMING FROM THE GENERATOR.
 PLEASE KNOW, THIS MAY BE DONE BY MORE
 THAN ONE WAY, HOWEVER PLEASE SEE GENERAC
 NOW DOES MAKE A NEW ATS WHICH MEETS CODE
 COMPLIANCE FOR THIS WHICH PROVIDES THE
 DISOCNNECTING MEANS FOR THE FPL/LINE
 SIDE AND A DISCONNECT FOR THE FEEDERS
 LOCATED IN THE SAME ATS. (RTSE).
 ** THIS IS NO WAY THE ONLY METHID, AND
 IS ONLY ONE IDEA).
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A RISER DIAGRAM
 INCLUDING ALL CONDUCTOR SIZES ANDHOW
 THIS WILL TIE INTO THE EXISTING
 SERVICE.
 PLEASE INDICATE OCP AND HOW THE NEW SE
 RATED ATS WILL BE FED. WHY ISTHIS UNIT
 SE RATED? PLEASE KNOW, THE METER MAIN IS
 STILL THE FIRST MEANS OF SERVICE
 DISCONNECT AND IT IS UNCLEAR HOW
 FEEDERS, OCP IS BEING CONNECTED AS SHOWN
 FROM EXISTING.
 PLEASE KNOW, IF THE NEW SE RATED ATS
 WILL BE THE NEW MAIN, MAY NOT PLACE LINE
 AND LOAD IN THE SMAE RACEWAY AND MAY NOT
 HAVE LINE IN W/ BRANCH CIRCUITS.230.7
 PLEASE CLARIFY AND SHOW THE DISCONNECT
 REQUIRED FOR FEEDERS FROM GEN TO HOUSE
 AND BEING GROUPED WITH THE EXISTING
 MAINS/DISCONNECTS.
 PLEASE SHOW AN OVERVIEW FOR LOCATION OF
 ALL EQUIPMENT ON PROPERTY
 240.4,310.16,215.5,225.31-225.39
  
 2) NOTE:OK, HOWEVER PLEASE VERIFY HOW
 LOAD FOR HEAT WENT DOWN? PLEASE SEE THE
 KW RATING AS SHOWN DOES NOT CORRELATE TO
 ANY COMMON HEAT STRIP.??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR HOUSE INCLUDING ALL
 LOADS.PLEASE KNOW ANY HEAT LOADS (AHU)
 SHALL BE AT 100%OR PLEASE PROVIDE A
 DETAIL ON HOW LOAD SHEDDING WILL TAKE
 PLACE.
 220.31
  
 3) NOTE: OK/NO, PLEASE SEE THE SETBACKS
 APPEAR TO BE OK, HOWEVER NO SPECS WERE
 SUBMITTED WHICH INDICATE THE MINIMUM
 CLEARENCES? PLEASE KNOW THE MIN REQUIRED
 WOULD BE 5FT.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE SETBACKS OF GEN
 FOR ALL SIDES FROM PROPERTY , AND ANY
 STRUCTURES.
 PLEASE SEE THAT THE MANUFACTURES SPECS
 SHOULD INCLUDE THE MIN CLEARENCES
 RECOMMENED BY MANUFACTURE.
 IT IS THE UNDERSTANDING FROM THE OFFICE
 FROM THE LTRS OBTAIN FROM THIS
 MANUFACTURE A MIN OF 5FT IS REQUIRED.
  
 4) NOTE: NO, THIS WAS NOT DONE AND FOUR
 DIFFERENT ATS MODELS,ONLY TWO COULD
 APPLY. PLEASE KNOW, AS THIS UNIT SEEMS
 TO BE TAKING THE PLACE OF THE MAIN FOR
 THE SERVICE, IT WOULD BE REQUIRED TO BE
 SE RATED. PLEASE SEE HOWEVER THE ABOVE
 COMMENT FOR THE REQUIRED DISCONNECTING
 MEANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO HIGH LIGHT
 UNITS/ EQUIPMENT BEING USED ON SPECS.
  
 5) NOTE: NO, THIS WAS NOTE TO SEE BBLDG
 COMMENTS, HOWEVER PLEASE SEE THERE ARE
 THREE DIFFERENT GENERATOR SLABS SHOWN ON
 PACKAGE. PLEASE SEE SURVEY SHOWS A SLAB
 WHICH DOES NOT CORRELATE TO EITHER THE
 ORIGINAL OR THE NEW ENGINEERING SLAB
 DETAILS SUBMITTED.
 PLEASE CORRELATE. THE NEW DETAIL
 SUBMITTED PROVIDES THE STRUCTURAL
 ATTACHMENT DETAIL REQUIRED PER NFPA-110
 CHAPTER 7.
  
 ** PREVIOUS REVIEW NOTE** PLEASE SEE
 BLDG REVIEW NOTES,
 AS INFORMATION IS REQUIRED ON HOW THE
 GENERATOR WILL BE ATTACHED TO THE SLAB.
 PLEASE ALSO PROVIDE MORE INFORMATION ON
 SLAB.
  
 ** NEW NOTE **
  
 6) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT PREVIOUSLY SUBMITTED AHS NOW
 EXPIRED PER FS 713.13(2). PLEASE KNOW,
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING NOC, THE NOC BECOMES VOID
 AND MUST BE RE-RECORDED.
 THIS IS ONLY REQUIRED BEFORE PICKING UP
 PERMIT.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS WITH RESPECT TO THE DESIGN
 PROFESSIONALS. PLEASE KNOW THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  