2006-07-21 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE PROVIDE A RISER DIAGRAM |
| INCLUDING ALL CONDUCTOR SIZES ANDHOW |
| THIS WILL TIE INTO THE EXISTING |
| SERVICE. |
| PLEASE INDICATE OCP AND HOW THE NEW SE |
| RATED ATS WILL BE FED. WHY ISTHIS UNIT |
| SE RATED? PLEASE KNOW, THE METER MAIN IS |
| STILL THE FIRST MEANS OF SERVICE |
| DISCONNECT AND IT IS UNCLEAR HOW |
| FEEDERS, OCP IS BEING CONNECTED AS SHOWN |
| FROM EXISTING. |
| PLEASE KNOW, IF THE NEW SE RATED ATS |
| WILL BE THE NEW MAIN, MAY NOT PLACE LINE |
| AND LOAD IN THE SMAE RACEWAY AND MAY NOT |
| HAVE LINE IN W/ BRANCH CIRCUITS.230.7 |
| PLEASE CLARIFY AND SHOW THE DISCONNECT |
| REQUIRED FOR FEEDERS FROM GEN TO HOUSE |
| AND BEING GROUPED WITH THE EXISTING |
| MAINS/DISCONNECTS. |
| PLEASE SHOW AN OVERVIEW FOR LOCATION OF |
| ALL EQUIPMENT ON PROPERTY |
| 240.4,310.16,215.5,225.31-225.39 |
| |
| 2) NOTE: PLEASE SUBMIT COMPLETE LOAD |
| CALCULATIONS FOR HOUSE INCLUDING ALL |
| LOADS.PLEASE KNOW ANY HEAT LOADS (AHU) |
| SHALL BE AT 100%OR PLEASE PROVIDE A |
| DETAIL ON HOW LOAD SHEDDING WILL TAKE |
| PLACE. |
| 220.31 |
| |
| 3) NOTE: PLEASE PROVIDE SETBACKS OF GEN |
| FOR ALL SIDES FROM PROPERTY , AND ANY |
| STRUCTURES. |
| PLEASE SEE THAT THE MANUFACTURES SPECS |
| SHOULD INCLUDE THE MIN CLEARENCES |
| RECOMMENED BY MANUFACTURE. |
| IT IS THE UNDERSTANDING FROM THE OFFICE |
| FROM THE LTRS OBTAIN FROM THIS |
| MANUFACTURE A MIN OF 5FT IS REQUIRED. |
| |
| 4) NOTE: PLEASE BE SURE TO HIGH LIGHT |
| UNITS/ EQUIPMENT BEING USED ON SPECS. |
| |
| 5) NOTE: PLEASE SEE BLDG REVIEW NOTES, |
| AS INFORMATION IS REQUIRED ON HOW THE |
| GENERATOR WILL BE ATTACHED TO THE SLAB. |
| PLEASE ALSO PROVIDE MORE INFORMATION ON |
| SLAB. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |