Plan Review Notes
Plan Review Notes For Permit 06070395
Permit Number 06070395
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-16 13:19:04** UNSAT **
  
 1) NOTE: PLEASE SEE THE SMOKE ALARMS ARE REQUIRED
 INSIDE AND OUTSIDE BEDROOM/SLEEPING ROOMS. PLEASE SEE
 LOCATION IS NOT AS SHOWN ON PREVIOUS PLANS. NFPA-72
 11.5.1.1
 THESE ARE SMOKE ALARMS NOT SMOKE DETECTORS AS SHOWN.
 THIS WAS REDLINED ON OTHER UNITS. SEE NFPA-72
 DEFINITIONS.
  
 2) NOTE: PLEASE SEE THE CIRCUIT FOR THE SMOKE ALARMS IS
 SHOWN ON CIRCUIT #8 WHEN PLANS INDICATE #10. PLEASE
 CORRELATE.
  
 3) NOTE: PLEASE SEE THE PANEL SCHEDULE IS SHOWING THE
 LOAD FOR WHAT APPEARS TO BE THE SECOND SMALL APPLIANCE
 CIRCUIT AT 450VA. IS THIS THE FRIG? PLEASE SEE THE
 PLANS ARE MISSING THE CIRCUIT NUNMBER DESIGNATION ON
 THE RECEPT IN KITCHEN NEXT TO PANEL. THIS DEVICE HAS
 TYPICALLY BEEN THE SECOND SMALL APPLIANCE IN OTHER
 UNITS.
 210.52B1, 210.11C1, 220.16
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717