Plan Review Notes
Plan Review Notes For Permit 06070197
Permit Number 06070197
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-08 00:00:00*** NOTES REDLINED ON PLANS ***
  
 1) NOTE: PLEASE SEE NFPA-101 7.9.2.2, IF
 AREA IN COOLER IS BEING LEFT IN TOTAL
 DARKNESS UPON THE TURNING OFF OF THE
 SWITHCES AS SHOWN, AN OCCUPANCY SENSOR
 OF SOME TYPE WILL BE REQUIRD INSIDE
 COOLER UNIT TO OVER RIDE LTS. THIS WILL
 ALLEAVIATE LEAVING AN OCCUPANT IN TOTAL
 DARKNESS FOR EGRESS IN THE EVENT THE
 SWITCHES BECOME ACCIDENTLY SWITCHED OFF.
 ** THE SIZE AND TRAVEL DISTANCE IN THIS
 COOLER IS SUBSTANTIAL AND WILL ALSO BE
 REQUIRED BY THE FIRE MARSHAL'S OFFICE.
  
 IF THERE ARE ANY QUESIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 VALUE FOR SCOPE PF WORK IS STILL IN NEED
 OF ADJUSTMENT TO INCLUDE ALL
 ELECTRICAL,MECHANICAL EQUIPMENT AND NEW
 COOLER.
 THE ELECTRICAL STATUS SHALL REMAIN IN
 "F" STATUES UNTIL ADJUSTMENT IS MADE. IF
 ONE IS NOT ADJUSTED BY CONTRACTOR, ONE
 WILL BE ADJUSTED PER MARSHAL'S & SWIFT
 GUIDES AS ADOPTED BY THE FBC 108.3