Plan Review Notes For Permit 06070197 |
Permit Number |
06070197 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-09-08 00:00:00 | *** NOTES REDLINED ON PLANS *** | | | | 1) NOTE: PLEASE SEE NFPA-101 7.9.2.2, IF | | AREA IN COOLER IS BEING LEFT IN TOTAL | | DARKNESS UPON THE TURNING OFF OF THE | | SWITHCES AS SHOWN, AN OCCUPANCY SENSOR | | OF SOME TYPE WILL BE REQUIRD INSIDE | | COOLER UNIT TO OVER RIDE LTS. THIS WILL | | ALLEAVIATE LEAVING AN OCCUPANT IN TOTAL | | DARKNESS FOR EGRESS IN THE EVENT THE | | SWITCHES BECOME ACCIDENTLY SWITCHED OFF. | | ** THE SIZE AND TRAVEL DISTANCE IN THIS | | COOLER IS SUBSTANTIAL AND WILL ALSO BE | | REQUIRED BY THE FIRE MARSHAL'S OFFICE. | | | | IF THERE ARE ANY QUESIONS, PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | VALUE FOR SCOPE PF WORK IS STILL IN NEED | | OF ADJUSTMENT TO INCLUDE ALL | | ELECTRICAL,MECHANICAL EQUIPMENT AND NEW | | COOLER. | | THE ELECTRICAL STATUS SHALL REMAIN IN | | "F" STATUES UNTIL ADJUSTMENT IS MADE. IF | | ONE IS NOT ADJUSTED BY CONTRACTOR, ONE | | WILL BE ADJUSTED PER MARSHAL'S & SWIFT | | GUIDES AS ADOPTED BY THE FBC 108.3 |
|