Plan Review Notes For Permit 06070197 |
Permit Number |
06070197 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-14 00:00:00 | *** DENIED *** | | 1) NOTICE OF COMMENCEMENT MUST HAVE THE | | FOLLOWING INFORMATION ADDED TO IT, | | *LEGAL DESCRIPTION OF PROPERTY,AND | | GENERAL DESCRIPTION OF IMPROVEMENTS. | | THEN REFILE WITH PALM BEACH COUNTY. | | | | 2) SHOW ON MECHANICAL PLAN HOW CONDENSER | | UNITS ARE TO BE ANCHORED TO CONDENSER | | STANDS AND HOW MANY STRAPS PER COMDENSER | | UNIT. BE ADVISED TIE DOWN CABLES ARE NOT | | PERMITTED OVER THE TOP OF A CONDENSER | | UNIT. | | | | 3) PLEASE ESTIMATE AMOUNT OF CONDENSATE | | WATER TO ENTER DRY WELL AND SIZE DRY | | WELL ACCORDINGLY. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|