2006-07-18 00:00:00 | ******** UNSAT ********* |
| |
| 1) NOTE: PLEASE SEE THE LIGHTING LAYOUT |
| WHICH WAS PROVIDED SEPARATELY NEEDS TO |
| CONTAIN CIRCUITING, CONTROLS AND |
| CORRELATE WITH THE SUBMITTED PANEL |
| SCHEDULE ON PLANS. IN FACT THE |
| ELECTRICLA LAYOUT SHOWN FOR COOLER |
| SHOULD BE PROVIDED BY THE DESIGN |
| PROFESSIONAL WHICH HAD DRAWN THE PLANS |
| FOR THE INSTALLATION OF COOLER AND ALL |
| OTHER ELECTRICAL WORK IN THIS SCOPE PF |
| WORK FOR THIS PERMIT FOR SPACE. |
| PLEASE KNOW, AS SCOPE OF WORK IS |
| PERMITTED AND DONE UNDER THE SAME |
| PERMIT. ONE DESIGN PROFESSIONAL SHOULD |
| BE RESPOSIBLE FOR DESIGN AND |
| CONNECTIONS, ETC ARE COMBINED. |
| 106.1.2 ADMIN SECT. PLEASE BE SURE TO |
| SEE 700.12E FOR CIRCUITIGN OF EM/EXT LTS |
| TO THE LOCAL LIGHTING BRANCH CIRCUIT IN |
| ANY ONE AREA. PLEASE KNOW, FAILURE OF |
| ONE OCP, CIRCUIT SHOULD NOT LEAVE IN ONE |
| AREA IN TOTAL DARKNESS. |
| LS 101 7.8, 7.9 |
| |
| 2) NOTE: PLEASE SEE RESPONSE LTR FROM |
| ARCHITECT'S OFFICE MENTIONS THE 2000 LS |
| CODE. PLEASE KNOW, WE ARE CURRENTLY |
| UNDER THE 2003 101. |
| |
| 3) NOTE: PLEASE SEE THAT THE SPECS ON EM |
| LTS ARE OK, HOWEVERTHERE IS A QUESTION |
| ON THE EM/EXT COMBO UNITWHERE THE |
| LISTING FOR THIS FIXTURE PERMITS THE |
| INSTALLATION IN THE COOLER/DAMP/POSSIBLE |
| WET LOCATION.? COULD NOT LOCATE ANY |
| INFORMATION ON SPECS SUBMITTED WHICH |
| LENDS TO THIS? |
| PLEASE ALSO SEE THE UNIT IS SHOWN AS A |
| COMBO UNIT WHICH IS FINE, HOWEVER PLANS |
| SHOULD INDICATE THIS. |
| 110.3, FBC 106.1.2 ADMIN SECT. |
| |
| 4) NOTE: PLEASE KNOW, IF ALL OTHER |
| ELECTRICAL MECHANICAL WORK IS INLCUDED |
| IN THE PERMIT/SCOPE, THEN PLEASE KNOW, |
| VALUATION FOR PERMIT SHALL INCLUDE ALL |
| LABOR AND MATERIALS WHETHER OR NOT ANY |
| OF THE EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3 |
| |
| THE EXTENSIVE RESPONSE LTR IS |
| APPRECIATED FOR CLARIFICATION OF OTHER |
| ITEMS. |
| |
| IF THERE ARE ANY QUESTIONS ON NOTE #1, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT THE ELECTRICAL PLANS, DESIGN ETC. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |