Plan Review Notes
Plan Review Notes For Permit 06070197
Permit Number 06070197
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-18 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE THE LIGHTING LAYOUT
 WHICH WAS PROVIDED SEPARATELY NEEDS TO
 CONTAIN CIRCUITING, CONTROLS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE ON PLANS. IN FACT THE
 ELECTRICLA LAYOUT SHOWN FOR COOLER
 SHOULD BE PROVIDED BY THE DESIGN
 PROFESSIONAL WHICH HAD DRAWN THE PLANS
 FOR THE INSTALLATION OF COOLER AND ALL
 OTHER ELECTRICAL WORK IN THIS SCOPE PF
 WORK FOR THIS PERMIT FOR SPACE.
 PLEASE KNOW, AS SCOPE OF WORK IS
 PERMITTED AND DONE UNDER THE SAME
 PERMIT. ONE DESIGN PROFESSIONAL SHOULD
 BE RESPOSIBLE FOR DESIGN AND
 CONNECTIONS, ETC ARE COMBINED.
 106.1.2 ADMIN SECT. PLEASE BE SURE TO
 SEE 700.12E FOR CIRCUITIGN OF EM/EXT LTS
 TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 ANY ONE AREA. PLEASE KNOW, FAILURE OF
 ONE OCP, CIRCUIT SHOULD NOT LEAVE IN ONE
 AREA IN TOTAL DARKNESS.
 LS 101 7.8, 7.9
  
 2) NOTE: PLEASE SEE RESPONSE LTR FROM
 ARCHITECT'S OFFICE MENTIONS THE 2000 LS
 CODE. PLEASE KNOW, WE ARE CURRENTLY
 UNDER THE 2003 101.
  
 3) NOTE: PLEASE SEE THAT THE SPECS ON EM
 LTS ARE OK, HOWEVERTHERE IS A QUESTION
 ON THE EM/EXT COMBO UNITWHERE THE
 LISTING FOR THIS FIXTURE PERMITS THE
 INSTALLATION IN THE COOLER/DAMP/POSSIBLE
 WET LOCATION.? COULD NOT LOCATE ANY
 INFORMATION ON SPECS SUBMITTED WHICH
 LENDS TO THIS?
 PLEASE ALSO SEE THE UNIT IS SHOWN AS A
 COMBO UNIT WHICH IS FINE, HOWEVER PLANS
 SHOULD INDICATE THIS.
 110.3, FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE KNOW, IF ALL OTHER
 ELECTRICAL MECHANICAL WORK IS INLCUDED
 IN THE PERMIT/SCOPE, THEN PLEASE KNOW,
 VALUATION FOR PERMIT SHALL INCLUDE ALL
 LABOR AND MATERIALS WHETHER OR NOT ANY
 OF THE EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
  
 THE EXTENSIVE RESPONSE LTR IS
 APPRECIATED FOR CLARIFICATION OF OTHER
 ITEMS.
  
 IF THERE ARE ANY QUESTIONS ON NOTE #1,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS, DESIGN ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]