Plan Review Notes For Permit 06070197 |
Permit Number |
06070197 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-01 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06070197 | | ADD: 5403 N HAVERHILL RD UNIT 31/32 | | CONT: PRIME MECHANICAL SERVICES | | TEL: (954)444-6823 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PLEASE PROVIDE THE LISTING REPORT | | WHICH PROVIDES THE DATA MEETING THE | | REQUIREMENTS OF 2603.4.1.2 COOLER AND | | FREEZER WALLS. | | | | 2) PLEASE PROVIDE THE FIRE SPRINKLER | | PLANS AS REQUIRED BY 2603.4.1.2(4)BE | | PROTECTED BY AN AUTOMATIC SPRINKLER | | SYSTEM. WHERE THE COOLER OR FREEZER IS | | WITHIN A BUILDING, BOTH THE COOLER OR | | FREEZER AND THAT PART OF THE BUILDING IN | | WHICH IT IS LOCATED SHALL BE | | SPRINKLERED. PROVIDE THE DETAILS HOW THE | | FIRE SPRINKLER HEADS WILL TRANSITION | | INTO THE FREEZER AND WALK IN COOLER. | | | | 3) ADDITIONAL INFORMATION REQUIRED | | 106.1.2*THERE IS NO INFORMATION AS HOW | | THE FREEZERS CEILING WILL BE FRAMED OR | | HOW IT WILL STAY IN PLACE? WILL IT BE | | ABLE TO TAKE ANY LOADING? | | | | 4) FEES DUE TO ADDITION OF FIRE REVIEW | | 10% OF PERMIT FEE. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|