Plan Review Notes
Plan Review Notes For Permit 06070197
Permit Number 06070197
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070197
 ADD: 5403 N HAVERHILL RD UNIT 31/32
 CONT: PRIME MECHANICAL SERVICES
 TEL: (954)444-6823
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE LISTING REPORT
 WHICH PROVIDES THE DATA MEETING THE
 REQUIREMENTS OF 2603.4.1.2 COOLER AND
 FREEZER WALLS.
  
 2) PLEASE PROVIDE THE FIRE SPRINKLER
 PLANS AS REQUIRED BY 2603.4.1.2(4)BE
 PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM. WHERE THE COOLER OR FREEZER IS
 WITHIN A BUILDING, BOTH THE COOLER OR
 FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE
 SPRINKLERED. PROVIDE THE DETAILS HOW THE
 FIRE SPRINKLER HEADS WILL TRANSITION
 INTO THE FREEZER AND WALK IN COOLER.
  
 3) ADDITIONAL INFORMATION REQUIRED
 106.1.2*THERE IS NO INFORMATION AS HOW
 THE FREEZERS CEILING WILL BE FRAMED OR
 HOW IT WILL STAY IN PLACE? WILL IT BE
 ABLE TO TAKE ANY LOADING?
  
 4) FEES DUE TO ADDITION OF FIRE REVIEW
 10% OF PERMIT FEE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026