2007-01-10 12:09:56** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS ARE NOW INCLUDING A NEW TANK
 LESS WATER HEATER WHICH HAS CREATED NEW COMMENTS.
 PLEASE SEE THIS CIRCUIT IS BEING SHOWN AS A SINGLE POLE
 20AMP CIRCUIT, HOWEVER THE LOAD ON THIS CIRCUIT IS
 SHOWN AS 3300VA. PLEASE SEE THAT THIS EXCEEDS THE
 MAXIMUM RATING ON THIS 20AMP SINGLE POLE CIRCUIT.
 PLEASE VERIFY THE SIZE OF THE CIRCUIT AND THE LOAD AND
 CORRELATE.
 310.16, 240.4, 408.4, 220 ETC.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UNIT BEING INSTALLED. PLEASE KNOW THIS
 DOCUMENTATION MUST CONTAIN THE INFORMATION AND
 LISTING(S) FROM A NRTL. NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 110.3, 90.7
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]