Plan Review Notes
Plan Review Notes For Permit 06070132
Permit Number 06070132
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-18 00:00:00*** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM THE
 PREVIOUS REVIEW AND ONE NEW COMMENT DUE
 TO CHANGE IN RISER.
 PLEASE SEE NOTES BELOEW ARE BEING TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WIHT NEW
 BEING ADDED TO THE BOTTOM OF REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE RESPONSE LETTER
 MENTIONS THAT SHEET "A-1" WAS REVISED,
 HOWEVER THESE COULD NOT BE LOCATED ON
 A-1. PLEASE EITHER REVISE ON A-1 OR
 ELECTRICAL SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE FOLLOWING
 CURRENT CODES IN EFFECT. PLEASE KNOW THE
 LATEST EDITION OF THE NEC IS NOT YET
 ADOPTED BY THE STATE OF FL.
 PLEASE LIST THE 2002 NFPA-70 (NEC), 2002
 NFPA-72 AND FBC 2004.
  
 2) NOTE: NO, NOT ENTIRELY. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 AS NOTED
 ON PREVIOUS REVIEW. PLEASE SEE ALL ROOMS
 AND OFFICES CONTAINING FLR TO CEILING
 HEIGHT PARTITIONS, SHALL CONTAIN
 SEPARATE CONTROLS FROM THE NORMAL TIMED
 SCHEDULING. PLEASE SEE CONTROLS SHOULD
 BE NOTED AND OVER RIDES TIMES (MAX)
 SAHLL BE STATED FOR THE DEVICE TYPE
 SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN
 A BUILDING GREATER THAN 5K SQ FT, IT
 WILL REQUIRE LIGHTING CONTROLS BY ONE
 METHOD AS MENTIONED. PLEASE EACH ROOM
 SHALL ALSO CONTAIN EITHER SOME TYPE OF
 OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE
 KNOWIF TIMER TYPE DEVICE IS USED, A
 MAX OF 4HR OF OVER RIDE, AND FOR
 OCCUPANCY SENSOR TYPE PERMITS A MAX OF
 30 MINS OF OVER RIDE. PLEASE SEE
 13-415.1.ABC.1.2, .1.3.
  
 3) NOTE: OK.
  
 4) NOTE: NO, THE COMMENT WAS ADDRESSED ,
 HOWEVER THE CONDUCTORS WERE REVISED.
 PLEASE SEE NEC 310.16, AS #4'S ARE ONLY
 RATED FOR 85A'S, AND WHEN THE CONDUCTOR
 SIZE DOES NOT CORRELATE TO THE STANDARD
 OCP DEVICE, THE CODES DOES PERMIT YOU TO
 GO TO THE NEXT SIZE UP, HOWEVER PLEASE
 SEE 240.6 AS THE NEXT SIZE OCP IS 90A'S
 AND THE RISER SHOWS 100A OCP ON THESE
 FEEDERS.
 PLEASE SEE 310.16 AND ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFYTHE CONDUCTORS
 SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND
 3-3#0, IT IS BEING TAKEN THIS IS A
 MISPRINT AND THE SYMBOLS ARE MEANING
 3/0?S. PLEASE SEE REDLINED PLANS FOR
 LOCATIONS AND ADJUST.
 310.16.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK, CAHNGED TO 100A.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  