2006-09-18 00:00:00 | *** UNSAT 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME COMMENTS FROM THE |
| PREVIOUS REVIEW AND ONE NEW COMMENT DUE |
| TO CHANGE IN RISER. |
| PLEASE SEE NOTES BELOEW ARE BEING TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW WIHT NEW |
| BEING ADDED TO THE BOTTOM OF REVIEW. |
| |
| |
| 1) NOTE: NO, PLEASE SEE RESPONSE LETTER |
| MENTIONS THAT SHEET "A-1" WAS REVISED, |
| HOWEVER THESE COULD NOT BE LOCATED ON |
| A-1. PLEASE EITHER REVISE ON A-1 OR |
| ELECTRICAL SHEETS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SPECIFY THE FOLLOWING |
| CURRENT CODES IN EFFECT. PLEASE KNOW THE |
| LATEST EDITION OF THE NEC IS NOT YET |
| ADOPTED BY THE STATE OF FL. |
| PLEASE LIST THE 2002 NFPA-70 (NEC), 2002 |
| NFPA-72 AND FBC 2004. |
| |
| 2) NOTE: NO, NOT ENTIRELY. PLEASE SEE |
| 13-415.1.ABC.1.1, .1.2 AND .1.3 AS NOTED |
| ON PREVIOUS REVIEW. PLEASE SEE ALL ROOMS |
| AND OFFICES CONTAINING FLR TO CEILING |
| HEIGHT PARTITIONS, SHALL CONTAIN |
| SEPARATE CONTROLS FROM THE NORMAL TIMED |
| SCHEDULING. PLEASE SEE CONTROLS SHOULD |
| BE NOTED AND OVER RIDES TIMES (MAX) |
| SAHLL BE STATED FOR THE DEVICE TYPE |
| SHOWN. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN |
| A BUILDING GREATER THAN 5K SQ FT, IT |
| WILL REQUIRE LIGHTING CONTROLS BY ONE |
| METHOD AS MENTIONED. PLEASE EACH ROOM |
| SHALL ALSO CONTAIN EITHER SOME TYPE OF |
| OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE |
| KNOWIF TIMER TYPE DEVICE IS USED, A |
| MAX OF 4HR OF OVER RIDE, AND FOR |
| OCCUPANCY SENSOR TYPE PERMITS A MAX OF |
| 30 MINS OF OVER RIDE. PLEASE SEE |
| 13-415.1.ABC.1.2, .1.3. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: NO, THE COMMENT WAS ADDRESSED , |
| HOWEVER THE CONDUCTORS WERE REVISED. |
| PLEASE SEE NEC 310.16, AS #4'S ARE ONLY |
| RATED FOR 85A'S, AND WHEN THE CONDUCTOR |
| SIZE DOES NOT CORRELATE TO THE STANDARD |
| OCP DEVICE, THE CODES DOES PERMIT YOU TO |
| GO TO THE NEXT SIZE UP, HOWEVER PLEASE |
| SEE 240.6 AS THE NEXT SIZE OCP IS 90A'S |
| AND THE RISER SHOWS 100A OCP ON THESE |
| FEEDERS. |
| PLEASE SEE 310.16 AND ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CLARIFYTHE CONDUCTORS |
| SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND |
| 3-3#0, IT IS BEING TAKEN THIS IS A |
| MISPRINT AND THE SYMBOLS ARE MEANING |
| 3/0?S. PLEASE SEE REDLINED PLANS FOR |
| LOCATIONS AND ADJUST. |
| 310.16. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK, CAHNGED TO 100A. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |