2006-07-24 00:00:00 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SPECIFY THE FOLLOWING |
| CURRENT CODES IN EFFECT. PLEASE KNOW THE |
| LATEST EDITION OF THE NEC IS NOT YET |
| ADOPTED BY THE STATE OF FL. |
| PLEASE LIST THE 2002 NFPA-70 (NEC), 2002 |
| NFPA-72 AND FBC 2004. |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN |
| A BUILDING GREATER THAN 5K SQ FT, IT |
| WILL REQUIRE LIGHTING CONTROLS BY ONE |
| METHOD AS MENTIONED. PLEASE EACH ROOM |
| SHALL ALSO CONTAIN EITHER SOME TYPE OF |
| OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE |
| KNOWIF TIMER TYPE DEVICE IS USED, A |
| MAX OF 4HR OF OVER RIDE, AND FOR |
| OCCUPANCY SENSOR TYPE PERMITS A MAX OF |
| 30 MINS OF OVER RIDE. PLEASE SEE |
| 13-415.1.ABC.1.2, .1.3. |
| |
| 3) NOTE: PLEASE SEE MISSING THE PRINTED |
| NAME AND PRINTED LICENSE NUMBER OF SAID |
| ARCHITECT ON TITLE BLOCKS AS REQUIRED |
| PER FAC 61G1-16.004. |
| THIS IS REQUIRED FOR ALL TRADES AND FOR |
| ALL SHEETS WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 4) NOTE: PLEASE CLARIFYTHE CONDUCTORS |
| SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND |
| 3-3#0, IT IS BEING TAKEN THIS IS A |
| MISPRINT AND THE SYMBOLS ARE MEANING |
| 3/0?S. PLEASE SEE REDLINED PLANS FOR |
| LOCATIONS AND ADJUST. |
| 310.16. |
| |
| 5) NOTE: PLEASE SEE 700.12E AS THE |
| EM/EXT LTS ARE REQUIRED TO BE CIRCUITED |
| AHEAD OFSWITCHING ON THE LOCAL |
| LIGHTING BRANCH CIRCUIT IN THE SAME |
| AREAS. |
| |
| 6) NOTE: PLEASE CLARIFY SPECIAL |
| EQUIPMENT LOAD OF 7500 VAON LOAD |
| CALCULATIONS AS THIS DOES NOT SEEM TO |
| CORRELATE WITH AMPERAGES ON PANEL |
| SCHEDULES. |
| PLEASE ALSO LIST THIS EQUIPMENT; SOME |
| NOTED FOR FUTURE HOWEVER PLEASE KNOW |
| EQUIPMENT MAY AFFECT INSTALLATION |
| REQUIREMENTS. |
| PLEASE ALSO SEE THAT WHEN THE NUMBER OF |
| RECEPTS ARE KNOW THE AMOUNT FIGURED FOR |
| LOAD CALCULATIONS SHALL BE 180VA PER |
| RECEPT. |
| PLEASE ALSO SEE PLANS APPEAR TO SHOW A |
| REFRIGIERATOR CIRCUITED TO OTHER GENERAL |
| RECEPT CIRCUIT? PLEASE VERIFY THE AMOUNT |
| OF VA ON THIS APPLIANCE AND PROVIDE A |
| DEDICATED CIRCUIT IF OVER 750VA. |
| 220.3,220.10,220.11,220.13 ETC. |
| 106.1.2 FBC ADMIN SECT. |
| |
| 7) NOTE: PLEASE CLARIFY RISER. IS THIS |
| 200A METER EXISTING FOR FUTURE USE AND |
| NOW BEING USED OR IS THIS NEW? PLEASE |
| LIST THE LOAD ON THE EXISTING SERVICE |
| ALONG WITH THE NEW LOAD ADDED. |
| 220,220.35 ETC. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |