Date |
Text |
2006-07-12 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW FOR A GAS PERMIT: |
| |
| 1. PER FBC-2004 CHAPTER 1 SECTION 106.1 |
| SUBMITTAL DOCUMENTS. CONSTRUCTION |
| DOCUMENTS, SPECIAL INSPECTION AND |
| STRUCTURAL OBSERVATION PROGRAMS, AND |
| OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| MORE SETS WITH EACH APPLICATION FOR A |
| PERMIT. ( NOTE ONLY ONE ISOMETRIC GAS |
| RISER DIAGRAM WAS SUBMITTED WITH PERMIT |
| APPLICATION. PERMIT APPLICATION |
| INDICATES TWO WATER HEATERS BUT THE GAS |
| ISOMETRIC RISER DIAGRAM ONLY INDCATES |
| ONE WATER HEATER, PLEASE CLARIFY FOR |
| RESUBMITTAL) |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 4. TYPE OF GAS, (LP OR NATURAL) PLEASE |
| INDICATE THIS ON DRAWING |
| 5. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| 6. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| (NOTE: THE LONGEST LENGTH METHOD IS USED |
| FOR SIZING GAS SYSTEMS, THE OTHER WATER |
| HEATER NEEDS TO BE INDICATED ON DRAWING |
| IN ORDER TO BE ABLE TO CHECK SIZING) |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| (NOTE: IF SYSTEM IS 2LB PLEASE SUBMIT |
| REGULATOR MANUFACTURE SHEETS) |
| 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |