Plan Review Notes
Plan Review Notes For Permit 06070123
Permit Number 06070123
Review Stop G
Sequence Number 1
Notes
Date Text
2006-07-12 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. PER FBC-2004 CHAPTER 1 SECTION 106.1
 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT. ( NOTE ONLY ONE ISOMETRIC GAS
 RISER DIAGRAM WAS SUBMITTED WITH PERMIT
 APPLICATION. PERMIT APPLICATION
 INDICATES TWO WATER HEATERS BUT THE GAS
 ISOMETRIC RISER DIAGRAM ONLY INDCATES
 ONE WATER HEATER, PLEASE CLARIFY FOR
 RESUBMITTAL)
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THIS ON DRAWING
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 (NOTE: THE LONGEST LENGTH METHOD IS USED
 FOR SIZING GAS SYSTEMS, THE OTHER WATER
 HEATER NEEDS TO BE INDICATED ON DRAWING
 IN ORDER TO BE ABLE TO CHECK SIZING)
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 (NOTE: IF SYSTEM IS 2LB PLEASE SUBMIT
 REGULATOR MANUFACTURE SHEETS)
 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved