Plan Review Notes
Plan Review Notes For Permit 06070109
Permit Number 06070109
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-29 13:06:08**** UNSAT 3RD REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
 COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND THEN NEW COMMENTS
 ARE ADDED TO BOTTOM.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK
  
 5) NOTE: OK.
  
 6) NOTE OK.
  
 7) NOTE:NO, OK, PLEASE SEE NEW NOTES FOR A REVISED
 RISER WHICH HAS NOW CHANGED A THIRD TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 OK, HOWEVER SEE NEW NOTES A
 COMPLETELY NEW RISER WAS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFTER DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK, STAIRS REMOVED.
  
 12) NOTE: OK, STAIRS REMOVED.
  
 13) NOTE:NO, SAME NOTE, PLEASE SEE PANEL SCHEDULE(S).
 IE: EXAMPLE: MASTER BDRM LT., KITCHEN LT'S, BERM #2
 RECEPTS, HALLWAY LT'S ETC
 IT IS KNOWN THAT DURING CONSTRUCTION THESE CIRCUITS AND
 LOCATIONS WILL CHANGE HOWEVER A MIN SCHEDULE FOR BRANCH
 CIRCUITS ARE REQUIRED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE SPECIFIC ROOMS
 AND AREAS ARE NOT LISTED ON PLANS.
  
 ** PREVIOUS REVIEW NOTEREVIEW #1**
 PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: OK, HOWEVER SEE NEW NOTE FOR OCP FOR STEAM
 UNIT.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: OK. HOWEVER SEE MINOR NEW NOTE FOR STEAM UNIT
 OCP.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:OK.
  
 21) NOTE: OK.
  
 22) NOTE:OK.
  
 23) NOTE: OK.
  
 24) NOTE: OK, PLEASE BE SURE ANY REVISED
 PLANS ARE ALSO SIGNED, ETC.
  
 25) NOTE:OK, PLEASE DO THE SAME AS NOTED ON BOTH
 PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE #2.
 OK, PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
 ***** NEW NOTES 2ND REVIEW ******
  
 26 ) NOTE: OK, HOWEVER SEE NEW NOTES FROM THIRD REVIEW
 PERTAINING TO REVISED SERVICE RISER.
  
 ** PREVIOUS REVIEW NOTE , REVIEW #2 **
 PLEASE SEE RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED.
 PLEASE SEE PLANS DO NOT SHOW THE
 LOCATION OF THIS NEW 400A MAIN. PLEASE
 SEE ALL MCB'S ARE BEING SHOWN AS BEING
 TAPPED FROM THIS ONE MAIN. PLEASE VERIFY
 TAPPED CONDUCTORS RULE W/ 240.21
 DEPENDING ON WHERE MAIN IS LOCATED.
 (VERIFY THE LUGS AVAILABLE FOR THREE
 CONDUCTORS, ONLY NOTED)
  
 27) NOTE: OK.
  
 28) NOTE: OK, MAIN NOW REMOVED?
  
 29) NOTE: OK, HOWEVER SEE NOTE FOR MIN SIZE ON NEW
 NOTES FOR GEC.
  
 30) NOTE: OK.
  
 31) NOTE:OK, SEE NEW NOTES.
  
  
 ** NEW NOTES 3RD REVIEW ***
  
  
 32) NOTE: PLEASE SEE SERVICE HAS NOW BEEN COMPLETELY
 REVISED REMOVING THE 400A MAIN DISCONNECT AND PROVIDING
 "TAPPED" CONDUCTORS FROM A NEW 480K-7 METER CAN. PLEASE
 SEE 310.15B6 CAN NO LONGER BE USED FOR THE SEC'S AS
 RISER SHOWN NO LONGER CAN USE EXCEPTION.
 310.15B6(HANDBOOK) 230.42A, 240.4 , 310.16 ETC. PLEASE
 SEE THE SEC'S IF BEING PROVIDED TO A FPL HAND-HOLE
 SHALL BE BASED ON THE 500A SERVICE BEING PROVIDED.
 PLEASE ALSO SEE TAPS(LUGS FOR 3CONDUCTORS ARE AVAILABLE
 FOR THE K-7, HOWEVER PLEASE VERIFY HOWCONDUCTORS ARE
 GOING TO BE INSTALLED AND THE LENGTH OF THE SEC'S FROM
 THE METER UNTIL THEY TERMINATE IN THE OCP DEVICE.
 PLEASE SEE 230.70 AS THE LENGTH INTO A BUILDING SHALL
 BE LIMITED TO THE NEAREST POINT OF ENTRANCE INTO A
 BLDG. THEPREVIOUS RISER SHOWED A MAIN WHICH WAS OK,
 AS LONG AS THE TAPPED CONDUCTORS MET 240.21, 408.16 AND
 THE LUGS WERE AVAILABLE FOR THE 400A MAIN DISCONNECT AS
 PREVIOUSLY NOTED AND THERE WERE "EQUIPMENT GROUNDING
 CONDUCTORS TO EACH PANEL WHICH WERE MISSING ON PREVIOUS
 RISER.(90.7,250.24B,250.122)
 PLEASE SEE AS SHOWN THE LENGTH OF SEC'S INTO THE
 DWELLING IS NOT PERMITTED TO BE MORE THAN 8FT (TOTAL
 LENGTH) OF UNPROTECTED CONDUCTOR 230.70, 90.4.
  
 ** PLEASE SEE THE PANEL "B" IS SHOWN WITH A 150A MCB
 WITH 3/0'S? THIS ISOK, HOWEVER ONLY NOTED. **PLEASE
 SEE THE FOLLOWWING COMMENTS AS THE SIZE OF THE SEC'S
 AND SERVICE ALSO AFFECTS THE GEC.
  
 33) NOTE: PLEASE PROVIDE COMPLETE NEUTRAL LOAD
 CALCULATIONS FOR THE NEUTRAL LOAD AS THE SEC NEUTRAL IS
 NOW BEING SHOWN 4 TIMES SMALLER THAN THE OTHER PHASE
 SEC'S, OR ADJUST THE SEC FOR THE NEUTRAL FOR FULL
 SIZE.220.22, 310.16
  
 34) NOTE: PLEASE SEE BASED ON NEW NOTES FROM THIRD
 REVIEW AND NOT KNOWING HOW LARGE WILL BE OR IF RISER
 WILL BE REVISED, PLEASE SEE 250.66 AS THE GEC IS
 REQUIRED TO BE SIZED FOR THE SEC'S. PLEASE SEE 310.16,
 AS THIS WOULD BE REFLECTED TO A 2/0 MIN.
 THIS IS NOTED AT THIS TIME BASED ON RISER AS SHOWN.
  
 35) NOTE: PLEASE SEE OCP AS NOTED ON SPECS FOR STEAM
 UNIT, INDICATES 35A OCP TO BE USED, HOWEVER PANEL
 SCHEDULE/CALCS INDICATE 40A. THIS IS AN ITEM WHICH
 COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER CORRECTIONS AT THIS TIME. PLEASE ADJUST.
  
 36) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT
 SUBMITTED IS LONGER VALID AND WILL BE REQUIRED TO BE
 RE-RECORDED. PLEASE SEE FS 713.13(2) . IF WORK HAS NOT
 COMMENCES WITHIN 90DAYS OF RECORDING NOC, THE NOC IS NO
 LONGER VALID AND SHALL BECOME VOID. THIS ONLY NEEDS TO
 BE RE-RECORDED AND IS ONLY REQUIRED WHEN PICKING UP
 PERMIT.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]