Date |
Text |
2006-10-29 13:06:08 | **** UNSAT 3RD REVIEW **** |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW AND SOME NEW COMMENTS |
| DUE TO CHANGES IN PLANS. |
| COMMENTS BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW AND THEN NEW COMMENTS |
| ARE ADDED TO BOTTOM. |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE OK. |
| |
| 7) NOTE:NO, OK, PLEASE SEE NEW NOTES FOR A REVISED |
| RISER WHICH HAS NOW CHANGED A THIRD TIME. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #2 ** |
| OK, HOWEVER SEE NEW NOTES A |
| COMPLETELY NEW RISER WAS SUBMITTED. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE VERIFY THE SIZE OF MAIN |
| AND METER, AS THE 320A OF METER AND THE |
| LOADS CALCS AFTER DERATINGS, EXCEED |
| THIS? |
| PLEASE ADJUST AND INCREASE SIZE OF |
| EQUIPMENT AS REQUIRED. |
| 230.70,240 ETC. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK, STAIRS REMOVED. |
| |
| 12) NOTE: OK, STAIRS REMOVED. |
| |
| 13) NOTE:NO, SAME NOTE, PLEASE SEE PANEL SCHEDULE(S). |
| IE: EXAMPLE: MASTER BDRM LT., KITCHEN LT'S, BERM #2 |
| RECEPTS, HALLWAY LT'S ETC |
| IT IS KNOWN THAT DURING CONSTRUCTION THESE CIRCUITS AND |
| LOCATIONS WILL CHANGE HOWEVER A MIN SCHEDULE FOR BRANCH |
| CIRCUITS ARE REQUIRED AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #2** |
| NO, PLEASE SEE SPECIFIC ROOMS |
| AND AREAS ARE NOT LISTED ON PLANS. |
| |
| ** PREVIOUS REVIEW NOTEREVIEW #1** |
| PLEASE SUBMIT AND COMPLETE THE |
| PANEL SCHEDULES INDICATING ALL |
| CIRCUITS, WIRE SIZES, AND OCP FOR EACH. |
| CIRCUITS SHALL BE SPECIFIC TO RMS AND |
| AREAS. |
| 408.4, 240.4, 310.16 ETC. |
| PLEASE SEE NOTES ABOVE AS MANY ITEMS ON |
| PLANS, DO NOT MATCH. |
| |
| 14) NOTE: OK, HOWEVER SEE NEW NOTE FOR OCP FOR STEAM |
| UNIT. |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE: OK. |
| |
| 17) NOTE: OK. HOWEVER SEE MINOR NEW NOTE FOR STEAM UNIT |
| OCP. |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE: OK. |
| |
| 20) NOTE:OK. |
| |
| 21) NOTE: OK. |
| |
| 22) NOTE:OK. |
| |
| 23) NOTE: OK. |
| |
| 24) NOTE: OK, PLEASE BE SURE ANY REVISED |
| PLANS ARE ALSO SIGNED, ETC. |
| |
| 25) NOTE:OK, PLEASE DO THE SAME AS NOTED ON BOTH |
| PREVIOUS REVIEW. |
| |
| ** PREVIOUS REVIEW NOTE #2. |
| OK, PLEASE BE SURE TO DO THE |
| SAME WHEN RESUBMITTING. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| ** IMPORTANT** |
| PLEASE KNOW, ONCE ALL REVIEWS ARE DONE |
| AND BEFORE RESUBMITTING PLANS. PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. ONLY ONE COPY |
| OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE. |
| PLEASE KNOW, THIS WILL HELP TO |
| ALLEVIATE ANY DELAYS INT THE PROCESSING |
| OF PROJECT FOR PERMIT. |
| |
| ***** NEW NOTES 2ND REVIEW ****** |
| |
| 26 ) NOTE: OK, HOWEVER SEE NEW NOTES FROM THIRD REVIEW |
| PERTAINING TO REVISED SERVICE RISER. |
| |
| ** PREVIOUS REVIEW NOTE , REVIEW #2 ** |
| PLEASE SEE RISER DIAGRAM HAS |
| NOW BEEN COMPLETELY REVISED. |
| PLEASE SEE PLANS DO NOT SHOW THE |
| LOCATION OF THIS NEW 400A MAIN. PLEASE |
| SEE ALL MCB'S ARE BEING SHOWN AS BEING |
| TAPPED FROM THIS ONE MAIN. PLEASE VERIFY |
| TAPPED CONDUCTORS RULE W/ 240.21 |
| DEPENDING ON WHERE MAIN IS LOCATED. |
| (VERIFY THE LUGS AVAILABLE FOR THREE |
| CONDUCTORS, ONLY NOTED) |
| |
| 27) NOTE: OK. |
| |
| 28) NOTE: OK, MAIN NOW REMOVED? |
| |
| 29) NOTE: OK, HOWEVER SEE NOTE FOR MIN SIZE ON NEW |
| NOTES FOR GEC. |
| |
| 30) NOTE: OK. |
| |
| 31) NOTE:OK, SEE NEW NOTES. |
| |
| |
| ** NEW NOTES 3RD REVIEW *** |
| |
| |
| 32) NOTE: PLEASE SEE SERVICE HAS NOW BEEN COMPLETELY |
| REVISED REMOVING THE 400A MAIN DISCONNECT AND PROVIDING |
| "TAPPED" CONDUCTORS FROM A NEW 480K-7 METER CAN. PLEASE |
| SEE 310.15B6 CAN NO LONGER BE USED FOR THE SEC'S AS |
| RISER SHOWN NO LONGER CAN USE EXCEPTION. |
| 310.15B6(HANDBOOK) 230.42A, 240.4 , 310.16 ETC. PLEASE |
| SEE THE SEC'S IF BEING PROVIDED TO A FPL HAND-HOLE |
| SHALL BE BASED ON THE 500A SERVICE BEING PROVIDED. |
| PLEASE ALSO SEE TAPS(LUGS FOR 3CONDUCTORS ARE AVAILABLE |
| FOR THE K-7, HOWEVER PLEASE VERIFY HOWCONDUCTORS ARE |
| GOING TO BE INSTALLED AND THE LENGTH OF THE SEC'S FROM |
| THE METER UNTIL THEY TERMINATE IN THE OCP DEVICE. |
| PLEASE SEE 230.70 AS THE LENGTH INTO A BUILDING SHALL |
| BE LIMITED TO THE NEAREST POINT OF ENTRANCE INTO A |
| BLDG. THEPREVIOUS RISER SHOWED A MAIN WHICH WAS OK, |
| AS LONG AS THE TAPPED CONDUCTORS MET 240.21, 408.16 AND |
| THE LUGS WERE AVAILABLE FOR THE 400A MAIN DISCONNECT AS |
| PREVIOUSLY NOTED AND THERE WERE "EQUIPMENT GROUNDING |
| CONDUCTORS TO EACH PANEL WHICH WERE MISSING ON PREVIOUS |
| RISER.(90.7,250.24B,250.122) |
| PLEASE SEE AS SHOWN THE LENGTH OF SEC'S INTO THE |
| DWELLING IS NOT PERMITTED TO BE MORE THAN 8FT (TOTAL |
| LENGTH) OF UNPROTECTED CONDUCTOR 230.70, 90.4. |
| |
| ** PLEASE SEE THE PANEL "B" IS SHOWN WITH A 150A MCB |
| WITH 3/0'S? THIS ISOK, HOWEVER ONLY NOTED. **PLEASE |
| SEE THE FOLLOWWING COMMENTS AS THE SIZE OF THE SEC'S |
| AND SERVICE ALSO AFFECTS THE GEC. |
| |
| 33) NOTE: PLEASE PROVIDE COMPLETE NEUTRAL LOAD |
| CALCULATIONS FOR THE NEUTRAL LOAD AS THE SEC NEUTRAL IS |
| NOW BEING SHOWN 4 TIMES SMALLER THAN THE OTHER PHASE |
| SEC'S, OR ADJUST THE SEC FOR THE NEUTRAL FOR FULL |
| SIZE.220.22, 310.16 |
| |
| 34) NOTE: PLEASE SEE BASED ON NEW NOTES FROM THIRD |
| REVIEW AND NOT KNOWING HOW LARGE WILL BE OR IF RISER |
| WILL BE REVISED, PLEASE SEE 250.66 AS THE GEC IS |
| REQUIRED TO BE SIZED FOR THE SEC'S. PLEASE SEE 310.16, |
| AS THIS WOULD BE REFLECTED TO A 2/0 MIN. |
| THIS IS NOTED AT THIS TIME BASED ON RISER AS SHOWN. |
| |
| 35) NOTE: PLEASE SEE OCP AS NOTED ON SPECS FOR STEAM |
| UNIT, INDICATES 35A OCP TO BE USED, HOWEVER PANEL |
| SCHEDULE/CALCS INDICATE 40A. THIS IS AN ITEM WHICH |
| COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING BACK |
| FOR OTHER CORRECTIONS AT THIS TIME. PLEASE ADJUST. |
| |
| 36) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT |
| SUBMITTED IS LONGER VALID AND WILL BE REQUIRED TO BE |
| RE-RECORDED. PLEASE SEE FS 713.13(2) . IF WORK HAS NOT |
| COMMENCES WITHIN 90DAYS OF RECORDING NOC, THE NOC IS NO |
| LONGER VALID AND SHALL BECOME VOID. THIS ONLY NEEDS TO |
| BE RE-RECORDED AND IS ONLY REQUIRED WHEN PICKING UP |
| PERMIT. |
| |
| |
| *** PLEASE SEE NOTE AS FIRST MENTIONED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |