Plan Review Notes
Plan Review Notes For Permit 06070109
Permit Number 06070109
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-23 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
 COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND THEN NEW COMMENTS
 ARE ADDED TO BOTTOM.
  
  
 ***** UNSAT *****
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 COMMENTS AND SOME ITEMS NOT COMPLETE AT
 THIS TIME, THERE MAY BE COMMENTS OTHER
 THAN BELOW ON THE NEXT REVIEW.
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE SOME ITEMS WERE
 ADDED AND SOME WERE CORRECTED, HOWEVER
 PLEASE SEE LOAD CALCULATIONS. PLEASE
 KNOW, THE LARGER OF THE TWO LOADS OF AN
 A/C CU AND AHU SHOULD BE FIGURED INTO
 THE LOAD CALCULATIONS. PLEASE SEE CU'S
 WITH LOADS LESS THAN HEAT BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE PLANS, PANEL
 SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS
 THAN IN PANEL SCHEDULES OR LOAD CALCS.
 PLEASE SEE ONLY ONE CU IS SHOWN ON
 PLANS, PLEASE SEE 3- AHU'S??
 106.1.2, 440.11 ETC
  
 5) NOTE: OK.
  
 6) NOTE OK.
  
 7) NOTE: OK, HOWEVER SEE NEW NOTES A
 COMPLETELY NEW RISER WAS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFTER DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: OK, HOWEVER SEE NOTE PERTAINING
 TO A/C LOADS.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK, STAIRS REMOVED.
  
 12) NOTE: OK, STAIRS REMOVED.
  
 13) NOTE: NO, PLEASE SEE SPECIFIC ROOMS
 AND AREAS ARE NOT LISTED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: NO, PLANS ONLY PROVIDE NOTES
 FOR WHERE THESE ARE GOING TO BE. NO
 DISCONNECTS, CLEARANCES, ACCESS IS BEING
 SHOWN. PLEASE SEE CODES BELOW AS
 CLEARANCES ETC CAN NOT BE VERIFIED.
 PLEASE SEE 240.24D ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL EQUIPMENT
 ON PLANS FOR STEAM UNITS, ELEVATOR
 EQUIPMENT, DISCONNECTS, LT'S, GFI ETC.
 UNABLE TO REVIEW LOCATIONS FOR CODE
 COMPLIANCE AT THIS TIME.
 110.26,240.4.240.24 ETC
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: NO, THESE COULD NOT BE LOCATED
 ON PLANS OR SUBMITTED IN PACKAGES.
 NEED TO VERIFY MIN CLEARANCES ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT MANUFACTURES
 SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT
 AND FOR STEAM UNIT EQUIPMENT. ALL SHALL
 INDICATE A LISTING FROM A NRTL.
 110.3, 106.1.2*
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:NO, PLEASE SEE A DINING RM
 CIRCUIT WAS ADDED ON PANEL SCHEDULE
 WHICH IS OK, HOWEVER IF THIS IS A
 DEDICATED CIRCUIT, THEN PLEASE SEE
 210.11C1, 220.16 FOR MIN VA TO BE
 FIGURED FOR THIS CIRCUIT.
 7-SM APPL CIRCUITS ARE LISTED ON PANEL
 SCHEDULE AND 7- SHOWN IN LOAD CALCS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1,
 210.11C1,220.16, DINING RM CIRCUIT SHALL
 BE INDICATED AS NOTED.
  
 21) NOTE: OK.
  
 22) NOTE:NO, PLEASE SEE DISCONNECT FOR
 CU OUTSIDE NOW, HAS BEEN MOVED BEHIND
 UNIT. THIS WAS SHOWN W/ CORRECT
 CLEARANCES ON PREVIOUS PLANS.
 PLEASE CLARIFY THE DISC'S FOR AHU'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 110.26 FOR MIN
 CLEARANCES FOR AHU'S AND DISCONNECTS.
  
 23) NOTE: OK.
  
 24) NOTE: OK, PLEASE BE SURE ANY REVISED
 PLANS ARE ALSO SIGNED, ETC.
  
 25) NOTE: OK, PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING.
  
 ** PREVIOUS REVIEW NOTE **
 ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEAS BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
 ***** NEW NOTES ******
  
 26 ) NOTE: PLEASE SEE RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED.
 PLEASE SEE PLANS DO NOT SHOW THE
 LOCATION OF THIS NEW 400A MAIN. PLEASE
 SEE ALL MCB'S ARE BEING SHOWN AS BEING
 TAPPED FROM THIS ONE MAIN. PLEASE VERIFY
 TAPPED CONDUCTORS RULE W/ 240.21
 DEPENDING ON WHERE MAIN IS LOCATED.
 (VERIFY THE LUGS AVAILABLE FOR THREE
 CONDUCTORS, ONLY NOTED)
  
 27) NOTE: PLEASE SEE ITEMS WHICH ARE NOW
 HAND WRITTEN ON RISER AND PLANS WHICH IS
 NOT PERMITTED. THESE ITEMS SHOULD BE
 PRINTED WHEN PLANS ARE RE-PRINTED.
 FBC ADMIN SECT 106.1
  
 28) NOTE: PLEASE SEE NOW THAT RISER HAS
 BEEN REVISED, PLEASE SEE MISSING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 THE MAIN TO THE SUB-PANELS.
 PLEASE SEE 250.24B, 250.110, AND TABLES
 IN 250.122 FOR SIZING.
  
 29) NOTE: PLEASE SEE MISSING CONNECTIONS
 FOR GROUNDING ELECTRODE SYSTEM TO BE
 COLD WATER PIPE (IF METAL), NEW FOOTER
 STEEL AND ANY OTHER SYSTEMS BEING
 PROVIDED. PLEASE SHOW ON RISER.
 250.50
 THIS WAS NOT IN PREVIOUS REVIEW NOTES
  
 30) NOTE: PLEASE SEE POOL PUMP AND POOL
 HEATER SHOULD BE NOTED AS (FUTURE) SINCE
 THESE ARE NOT SHOWN ON PLANS AND POOL IS
 NOT PERMITTED AT THIS TIME.
  
 31) NOTE: PLEASE SEEFS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 THIS IS ONLY A NOTICE.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]