2006-07-12 00:00:00 | DENIED; | | 1.RISER DIAGRAM DOES NOT MATCH FLOOR | | PLAN. (NO BATHROOM NEXT TO KITCHEN) | | 2.BOTH BIDETS ARE NOT VENTED. (TOILET | | FLUSHES PAST BIDET NO VENT) | | 3.PLEASE SIZE TRUNK LINE ALL THE WAY TO | | KITCHEN. | | 4. MASTER BATH FIRST FLOOR LAV STACK CAN | | NOT BE INSTALLED AS DRAWN. (DOOR BETWEEN | | LAVS) | | ONE SET OF PLANS MARKED IN RED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|