Plan Review Notes
Plan Review Notes For Permit 06070109
Permit Number 06070109
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-08 00:00:00 
 ***** UNSAT *****
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 COMMENTS AND SOME ITEMS NOT COMPLETE AT
 THIS TIME, THERE MAY BE COMMENTS OTHER
 THAN BELOW ON THE NEXT REVIEW.
  
  
 1) NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. PLEASE SEE MANY LOCATIONS ON
 PLANS.2',6',12' RULE.
  
 2) NOTE: PLEASE SEE MISSING RECEPTS FOR
 KITCHEN ISLAND, FOR ALL ELECTRICAL
 APPLIANCES, COUNTERSPACE ETC. PLEASE
 COMPLETE.
 PLEASE SEE 210.52C1-5, 210.8A6, FBC
 ADMIN SECT 106.1.2
  
 3) NOTE: PLEASE KNOW, SD'S SHALL BE
 LOCATED WITH IN 3' OF THE PEAK ON A
 SLPOED CEILING AND SHALL BE WITHIN 12"
 OF THE HIGHEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
 PLEASE ALSO SEE AREAS WHICH REQUIRE
 SD'S IN THE IMMEDIATE VICINITY OUTSIDE
 ALL SLEEPING RMS.
 11.5.1.1
  
 4) NOTE: PLEASE CORRELATE PLANS, PANEL
 SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS
 THAN IN PANEL SCHEDULES OR LOAD CALCS.
 PLEASE SEE ONLY ONE CU IS SHOWN ON
 PLANS, PLEASE SEE 3- AHU'S??
 106.1.2, 440.11 ETC
  
 5) NOTE: PLEASE SEE MISSING GFI RECEPT
 PER 210.6 FOR CU'S.
  
 6) NOTE PLEASE PROVIDE AIC RATINGS FOR
 MAIN(S). 110.9, ONLY SHOWN FOR SUB
 PANELS AND THE SERIES RATINGS.
  
 7) NOTE: PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFETR DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: PLEASE CORRLEATE PLANS, PANELS,
 AND LOAD CALCS. PLEASE SEE PLANS
 INDICATE MORE THAN ONE WASHER AND DRYER.
 ADJUST AS REQUIRED.
 220.31, 215.5, 310.16, *106.1.2
  
 9) NOTE: PLEASE SEE LOADS SHOWN FOR
 WATER HEATER EXCEED BRANCH CIRCUIT
 RATING. 9KW? ON 30A BRKR?
 240.4,310.16, 240, 220 ETC
  
 10) NOTE: PLEASE SEE LOAD FOR STEAM UNIT
 EXCEEDS BRANCH CIRCUIT RATING FOR THE
 1-POLE 40A BRKR.
 240.4,310.16,240.,220 ETC
  
 11) NOTE: PLEASE PROVIDE AN ELEVATION OF
 ELECTRICAL SERVICE INCORPORATED WITH
 STAIRS ON OUTSIDE WALL.
 PLEASE SEE 110.26 AND MIN CLEARNECES
 REQUIRED BY FPL FOR LOCATION AS SHOWN.
  
 12) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL REQUIRED FOR OUTSIDE
 STAIRS AT LOWER LEVEL. (3-WAY). LS 101
 7.8, NEC 210.70
  
 13) NOTE: PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATTING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: PLEASE INDICATE ALL EQUIPMENT
 ON PLANS FOR STEAN UNITS, ELEVATOR
 EQUIPMENT, DISCONNECTS, LTS, GFI ETC.
 UNABLE TO REVIEW LOCATIONS FOR CODE
 COMPLIANCE AT THIS TIME.
 110.26,240.4.240.24 ETC
  
 15) NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 16) NOTE: PLEASE SEE ENERGY CALCS
 SHALLBE SIGNED , DATED AND SEALED.
 PLEASE SEE FBC CHAPTER 13
 FS 481.221, 471.023
  
 17) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT
 AND FOR STEAM UNIT EQUIPMENT. ALL SHALL
 INDICATE A LISTING FROM A NRTL.
 110.3, 106.1.2*
  
 18) NOTE: PLEASE CLARIFY EXTERIOR LTS ON
 A 220V CIRCUIT??
 310.16, 220.,240.4 ETC
  
 19) NOTE: PLEASE INDICATE THE DEDICATED
 BATH(S) CIRCUIT(S0 PER 210.52D,210.11C3,
 MUST BE 20A AND #12.
  
 20) NOTE: PLEASE SEE 210.52B1,
 210.11C1,220.16, DINING RM CIRCUIT SHALL
 BE INDICATED AS NOTED.
  
 21) NOTE: PLEASE SEE PLANS NOTE ARC
 FAULT FOR WALL OUTLETS, THIS HAS CHANGED
 IN THE 2002 NEC, WHICH WENT INTO EFFECT
 7/1/2003.
 ALL OUTLETS" , IN BEDRMS SHALL BE
 PROTECTED. , LTS, RECEPTS, FANS, SD'S
 ETC.
 PLEASE LIST ALL THE ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. A NOT IS NOT
 SUFFICIENT.
 210.12B, 408.4
  
 22) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES FOR AHU'S AND DISCONNECTS.
  
 23) NOTE: PLEASE SEE PLANS SHALL
 INDICATE THE 2002 NEC.
  
 24) NOTE: PLEASE SEE PLANS ARE NOT
 SIGNED, SEALED , OR DO NOT CONTAIN A
 TITLE BLOCK FOR PERSON RESPONSIBLE FOR
 PLASN AND DESIGN.
 PLEASE SEE THAT PLANS SHALL CLEARLY
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBEL FOR PLANS AND
 DESIGN. PLEASE SEE 106 FBC AND FS 481,
 471, 468 FOR PERSON PERMITTED TO DO
 SCOPE PF WORK AS SHOWN.
  
 25) NOTE: ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEAS BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]