2006-07-08 00:00:00 | |
| ***** UNSAT ***** |
| |
| ** PLEASE KNOW, DUE TO THE EXTENT OF |
| COMMENTS AND SOME ITEMS NOT COMPLETE AT |
| THIS TIME, THERE MAY BE COMMENTS OTHER |
| THAN BELOW ON THE NEXT REVIEW. |
| |
| |
| 1) NOTE: PLEASE SEE 210.52 FOR RECEPT |
| SPACING. PLEASE SEE MANY LOCATIONS ON |
| PLANS.2',6',12' RULE. |
| |
| 2) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| KITCHEN ISLAND, FOR ALL ELECTRICAL |
| APPLIANCES, COUNTERSPACE ETC. PLEASE |
| COMPLETE. |
| PLEASE SEE 210.52C1-5, 210.8A6, FBC |
| ADMIN SECT 106.1.2 |
| |
| 3) NOTE: PLEASE KNOW, SD'S SHALL BE |
| LOCATED WITH IN 3' OF THE PEAK ON A |
| SLPOED CEILING AND SHALL BE WITHIN 12" |
| OF THE HIGHEST POINT ON A FLAT CEILING. |
| NFPA-72 11.8.3 |
| PLEASE ALSO SEE AREAS WHICH REQUIRE |
| SD'S IN THE IMMEDIATE VICINITY OUTSIDE |
| ALL SLEEPING RMS. |
| 11.5.1.1 |
| |
| 4) NOTE: PLEASE CORRELATE PLANS, PANEL |
| SCHEDULES AND LOAD CALCULATIONS. |
| PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS |
| THAN IN PANEL SCHEDULES OR LOAD CALCS. |
| PLEASE SEE ONLY ONE CU IS SHOWN ON |
| PLANS, PLEASE SEE 3- AHU'S?? |
| 106.1.2, 440.11 ETC |
| |
| 5) NOTE: PLEASE SEE MISSING GFI RECEPT |
| PER 210.6 FOR CU'S. |
| |
| 6) NOTE PLEASE PROVIDE AIC RATINGS FOR |
| MAIN(S). 110.9, ONLY SHOWN FOR SUB |
| PANELS AND THE SERIES RATINGS. |
| |
| 7) NOTE: PLEASE VERIFY THE SIZE OF MAIN |
| AND METER, AS THE 320A OF METER AND THE |
| LOADS CALCS AFETR DERATINGS, EXCEED |
| THIS? |
| PLEASE ADJUST AND INCREASE SIZE OF |
| EQUIPMENT AS REQUIRED. |
| 230.70,240 ETC. |
| |
| 8) NOTE: PLEASE CORRLEATE PLANS, PANELS, |
| AND LOAD CALCS. PLEASE SEE PLANS |
| INDICATE MORE THAN ONE WASHER AND DRYER. |
| ADJUST AS REQUIRED. |
| 220.31, 215.5, 310.16, *106.1.2 |
| |
| 9) NOTE: PLEASE SEE LOADS SHOWN FOR |
| WATER HEATER EXCEED BRANCH CIRCUIT |
| RATING. 9KW? ON 30A BRKR? |
| 240.4,310.16, 240, 220 ETC |
| |
| 10) NOTE: PLEASE SEE LOAD FOR STEAM UNIT |
| EXCEEDS BRANCH CIRCUIT RATING FOR THE |
| 1-POLE 40A BRKR. |
| 240.4,310.16,240.,220 ETC |
| |
| 11) NOTE: PLEASE PROVIDE AN ELEVATION OF |
| ELECTRICAL SERVICE INCORPORATED WITH |
| STAIRS ON OUTSIDE WALL. |
| PLEASE SEE 110.26 AND MIN CLEARNECES |
| REQUIRED BY FPL FOR LOCATION AS SHOWN. |
| |
| 12) NOTE: PLEASE SEE MISSING EGRESS |
| LIGHTING CONTROL REQUIRED FOR OUTSIDE |
| STAIRS AT LOWER LEVEL. (3-WAY). LS 101 |
| 7.8, NEC 210.70 |
| |
| 13) NOTE: PLEASE SUBMIT AND COMPLETE THE |
| PANEL SCHEDULES INDICATTING ALL |
| CIRCUITS, WIRE SIZES, AND OCP FOR EACH. |
| CIRCUITS SHALL BE SPECIFIC TO RMS AND |
| AREAS. |
| 408.4, 240.4, 310.16 ETC. |
| PLEASE SEE NOTES ABOVE AS MANY ITEMS ON |
| PLANS, DO NOT MATCH. |
| |
| 14) NOTE: PLEASE INDICATE ALL EQUIPMENT |
| ON PLANS FOR STEAN UNITS, ELEVATOR |
| EQUIPMENT, DISCONNECTS, LTS, GFI ETC. |
| UNABLE TO REVIEW LOCATIONS FOR CODE |
| COMPLIANCE AT THIS TIME. |
| 110.26,240.4.240.24 ETC |
| |
| 15) NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 16) NOTE: PLEASE SEE ENERGY CALCS |
| SHALLBE SIGNED , DATED AND SEALED. |
| PLEASE SEE FBC CHAPTER 13 |
| FS 481.221, 471.023 |
| |
| 17) NOTE: PLEASE SUBMIT MANUFACTURES |
| SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT |
| AND FOR STEAM UNIT EQUIPMENT. ALL SHALL |
| INDICATE A LISTING FROM A NRTL. |
| 110.3, 106.1.2* |
| |
| 18) NOTE: PLEASE CLARIFY EXTERIOR LTS ON |
| A 220V CIRCUIT?? |
| 310.16, 220.,240.4 ETC |
| |
| 19) NOTE: PLEASE INDICATE THE DEDICATED |
| BATH(S) CIRCUIT(S0 PER 210.52D,210.11C3, |
| MUST BE 20A AND #12. |
| |
| 20) NOTE: PLEASE SEE 210.52B1, |
| 210.11C1,220.16, DINING RM CIRCUIT SHALL |
| BE INDICATED AS NOTED. |
| |
| 21) NOTE: PLEASE SEE PLANS NOTE ARC |
| FAULT FOR WALL OUTLETS, THIS HAS CHANGED |
| IN THE 2002 NEC, WHICH WENT INTO EFFECT |
| 7/1/2003. |
| ALL OUTLETS" , IN BEDRMS SHALL BE |
| PROTECTED. , LTS, RECEPTS, FANS, SD'S |
| ETC. |
| PLEASE LIST ALL THE ARC FAULT PROTECTED |
| CIRCUITS ON PANEL SCHEDULE. A NOT IS NOT |
| SUFFICIENT. |
| 210.12B, 408.4 |
| |
| 22) NOTE: PLEASE SEE 110.26 FOR MIN |
| CLEARENCES FOR AHU'S AND DISCONNECTS. |
| |
| 23) NOTE: PLEASE SEE PLANS SHALL |
| INDICATE THE 2002 NEC. |
| |
| 24) NOTE: PLEASE SEE PLANS ARE NOT |
| SIGNED, SEALED , OR DO NOT CONTAIN A |
| TITLE BLOCK FOR PERSON RESPONSIBLE FOR |
| PLASN AND DESIGN. |
| PLEASE SEE THAT PLANS SHALL CLEARLY |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBEL FOR PLANS AND |
| DESIGN. PLEASE SEE 106 FBC AND FS 481, |
| 471, 468 FOR PERSON PERMITTED TO DO |
| SCOPE PF WORK AS SHOWN. |
| |
| 25) NOTE: ** IMPORTANT** |
| PLEASE KNOW, ONCE ALL REVIEWS ARE DONE |
| AND BEFORE RESUBMITTING PLANS. PLEAS BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. ONLY ONE COPY |
| OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE. |
| PLEASE KNOW, THIS WILL HELP TO |
| ALLEAVIATE ANY DELAYS INT THE PROCESSING |
| OF PROJECT FOR PERMIT. |
| |
| |
| *** PLEASE SEE NOTE AS FIRST MENTIONED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |