Plan Review Notes
Plan Review Notes For Permit 06070104
Permit Number 06070104
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
 _XX_4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 PLEASE TO TO WWW.FLORIDABUILDING.ORG AND
 PRINT THE FLORIDA STATE PRODUCT APPROVAL
 COVER SHEET FOR THIS PRODUCT.
  
 _XX_8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  
  
 NEW COMMENT:
  
 THE FLOOR PLAN WAS PROVIDED BUT DOES NOT
 SHOW SIZES.YOU HAVE CIRCLED -40PSF,
 12IN SPACING.IT IS NOT CLEAR FROM THE
 FLOOR PLAN IF ANY OPENINGS ARE IN ZONE
 5.20SF AND SMALLER OPENINGS IN ZONE 5
 WOULD HAVE A DESIGN PRESSURE GREATER
 THAN -40PSF.CODE COMPLIANCE CANNOT BE
 DETERMINED FROM THE INFORMATION
 PROVIDED.
  