2006-07-12 00:00:00 | *** DENIED *** |
| 1) OPEN FLOOR DRAINS CAN NOT BE IN A |
| MECHANICAL ROOM THAT IS AN OPEN PLENUM, |
| PER 2004 FBC/P 901.2, FBC/M 601.3, AND |
| ASHARE 8.4.1.11 . |
| |
| 2) PLANS THAT HAVE AN ENGINEER'S SEAL ON |
| THEM MUST ALSO HAVE THE ENGINEER'S |
| PRINTED NAME, ADDRESS, AND LICENSE |
| NUMBER ON EACH SHEET, PER FAC |
| 61G15-23.002 . |
| |
| 3) PLEASE HAVE JOB ADDRESS ADDED TO |
| TITLE BLOCK, PER 2004 FBC 106.1.1 . |
| |
| 4) PLEASE SHOW SIZE OF ALL RETURN AIR |
| TRANSFER DUCTS, SEE NOTE #5 (A). |
| |
| 5) BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |