Notes
Date Text
2006-07-15 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE CLARIFY THE ROOM IN
 WHICH THE NEW VAV PANEL IS BEING
 INSTALLED. PLEASE KNOW AND NOTE ON PLANS
 THAT THIS RM SHALL BE AN ELEC/MECH RM
 ONLY CONTAINING NO STORAGE.
 110.26,240.24,408.7 ETC.
 SIGNAGE REQUIRED ON DOOR STATING " NO
 STORAGE" OR WORDS TO THE EFFECT.
 MIN 1" ON CONTRASTING BACKGROUND.
  
 2) NOTE: PLEASE SPECIFY THE CURRENT NEC
 ( NFPA-70) OF 2002. PLANS NOTE THE
 LATEST EDITION, HOWEVER THE LATEST NEC
 (2005 ) HAS NOT BEEN ADOPTED AS OF YET.
  
 3) NOTE: PLEASE SEE TITLE BLOCKS OF
 SHEET SHOULD CORRELATE AS A-SHEETS
 MENTIONS THE GOVERNMENTAL BUILDING, YET
 E-SHEETS MENTIONS THE ADMINISTRATIVE
 OFFICE COMPLEX WHICH IS NOT THE SAME.
 PLEASE KNOW, PER THE PERMIT APPLICATION,
 WORK IS APPLIED FOR UNDER 301 N OLIVE
 WHICH SHOULD BE REFLECTED ON PLANS,
 WHICH IS THE GOV. CENTER.
  
 4) NOTE: NOTE ON PLANS MENTIONS ROUTING
 OF NEW CONDUIT AND MENTIONS NEW PANEL
 NEAR STAIRWELL, PLEASE KNOW, THE FEEDERS
 AND CONDUIT MAY NOT BE RUN IN STAIRWAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  