2006-07-15 00:00:00 | **** UNSAT **** |
| |
| 1) NOTE: PLEASE CLARIFY THE ROOM IN |
| WHICH THE NEW VAV PANEL IS BEING |
| INSTALLED. PLEASE KNOW AND NOTE ON PLANS |
| THAT THIS RM SHALL BE AN ELEC/MECH RM |
| ONLY CONTAINING NO STORAGE. |
| 110.26,240.24,408.7 ETC. |
| SIGNAGE REQUIRED ON DOOR STATING " NO |
| STORAGE" OR WORDS TO THE EFFECT. |
| MIN 1" ON CONTRASTING BACKGROUND. |
| |
| 2) NOTE: PLEASE SPECIFY THE CURRENT NEC |
| ( NFPA-70) OF 2002. PLANS NOTE THE |
| LATEST EDITION, HOWEVER THE LATEST NEC |
| (2005 ) HAS NOT BEEN ADOPTED AS OF YET. |
| |
| 3) NOTE: PLEASE SEE TITLE BLOCKS OF |
| SHEET SHOULD CORRELATE AS A-SHEETS |
| MENTIONS THE GOVERNMENTAL BUILDING, YET |
| E-SHEETS MENTIONS THE ADMINISTRATIVE |
| OFFICE COMPLEX WHICH IS NOT THE SAME. |
| PLEASE KNOW, PER THE PERMIT APPLICATION, |
| WORK IS APPLIED FOR UNDER 301 N OLIVE |
| WHICH SHOULD BE REFLECTED ON PLANS, |
| WHICH IS THE GOV. CENTER. |
| |
| 4) NOTE: NOTE ON PLANS MENTIONS ROUTING |
| OF NEW CONDUIT AND MENTIONS NEW PANEL |
| NEAR STAIRWELL, PLEASE KNOW, THE FEEDERS |
| AND CONDUIT MAY NOT BE RUN IN STAIRWAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |