2006-07-31 00:00:00 | PLANNING AND ZONING DEPARTMENT:FAILED |
| |
| 1.PROVIDE A BETTER DETAIL OF THE AREA |
| WHERE THE GENERATOR IS PROPOSED, NOT AN ENLARGEMENT. |
| THE SURVEY SHALL INCLUDE |
| THE FOLLOWING: |
| |
| A. SCREENING AND ELEVATION OF |
| WALL/HEDGES AROUND GENERATOR/ FUEL TANK, |
| AND SETBACK DISTANCE FROM PROPERTY |
| LINE. |
| |
| 2.PURSUANT TO SECTION 94-444(B) OPEN |
| SPACE STANDARDS: |
| (B) FUEL OR OIL OR PROPANE |
| TANKS, GENERATORS SHALL NOT BE PERMITTED |
| UNLESS APPROPRIATE SCREENING IS |
| PROVIDED. SCREENING SHALL BE CONSTRUCTED |
| OF BRICK, DECORATIVE CONCRETE, OTHER |
| DECORATIVE MASONRY, OR COMPARABLY |
| DURABLE WOOD AND STEEL. |
| |
| WALLS SHALL BE LANDSCAPED WITH SHRUBS |
| AND HEDGES PLANTED AT TWO-FOOT |
| INTERVALS.A FOUR-SIDED ENCLOSURE |
| WITH MASONRY, OR COMPARABLY DURABLE WOOD |
| AND STEEL, AN OBSCURING GATE IS REQUIRED |
| AS A CONDITION FOR SITE PLAN APPROVAL. |
| |
| THE SCREENING SHALL ENCLOSE BOTH FUEL |
| TANK INCLUDING ROOFTOP EXHAUST (TANK, IF APPLICABLE AND |
| GENERATOR. |
| |
| 3.PURSUANT TO SECTION 94-305(B)(4) |
| SETBACKS |
| (B)(4) SETBACK ENCROACHMENT: |
| MECHANICAL EQUIPMENT SHALL NOT PROJECT |
| MORE THAN 4 FEET INTO A SETBACK. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT ME AT THE NUMBER BELOW. |
| |