2006-07-31 00:00:00PLANNING AND ZONING DEPARTMENT:FAILED
  
 1.PROVIDE A BETTER DETAIL OF THE AREA
 WHERE THE GENERATOR IS PROPOSED, NOT AN ENLARGEMENT.
 THE SURVEY SHALL INCLUDE
 THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF
 WALL/HEDGES AROUND GENERATOR/ FUEL TANK,
 AND SETBACK DISTANCE FROM PROPERTY
 LINE.
  
 2.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE
 TANKS, GENERATORS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL, AN OBSCURING GATE IS REQUIRED
 AS A CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK, IF APPLICABLE AND
 GENERATOR.
  
 3.PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT
 MORE THAN 4 FEET INTO A SETBACK.
  