Plan Review Notes
Plan Review Notes For Permit 06070082
Permit Number 06070082
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00NOT REQUIRED AT THIS TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED.
 APPLICATION & INFORMATION FOR GAS PERMIT
 TO BE SUBMITTED WITH GAS APPLICATION.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
 GENERATOR SUBMITTAL SHEET INDICATES
 NATURAL GAS, BUT INFORMATION TO BE
 INDICATED ON GAS PERMIT APPLICATION
 INFORMATION.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. NOT USED.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INCLUDING THE INFORMATION FOR MINIMUM
 DISTANCE FROM WALLS, STRUCTURES ETC. PER
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]