2006-07-21 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE ADDRESS IS FOR |
| "OKEECHOBEE RD" PLEASE KNOW, LEGALLY |
| THERE IS NOT 'OLD " OKEECHOBEE IN THE |
| CITY OF WEST PALM BEACH. |
| PLEASE PLACE ADDRESS ON PLANS. |
| 1259 OKEECHOBEE RD. |
| |
| 2) NOTE: PLEASE SEE RISER DIAGRAM SHOWN A |
| SE RATED ATS , HOWEVER PLEASE SEE SPEC |
| SUBMITTED ARE HIGH LIGHTED FOR A NON-SSE |
| RATED ATS.? |
| PLEASE CLARIFY. |
| PLEASE ALSO CLARIFY OF THE EXISTING MAIN |
| SHOWN ON RISER IS NEXT TO OR GROUPED IN |
| CLOSE PROXIMITY TO NEW ATS/ SE RATED |
| MAIN. |
| 230.72,225.34 |
| 110.3,90.7 |
| |
| 3) NOTE: PLEASE SEE AN "EQUIPMENT |
| GROUNDING CONDUCTOR IS BEING SHOWN FROM |
| METER TO THE FIRST MEANS OF DISCONNET, |
| HOWEVER PER 250.6,250.24, ONLY AFTER THE |
| FIRST MEANS OF DISCONNECT, DOES AN |
| EQUIPMENT GROUNDING CONDUCTOR GET |
| INSTALLED. |
| |
| 4) NOTE: PLEASE KNOW, AS PER INFORMATION |
| OBTAINED BY THE OFFICE, THE MIN |
| CLEARENCES FOR THESE TYPE OF GEN SHOULD |
| BE 5' FROM ALL WALLS BLDGS ETC. PLEASE |
| KNOW, IF INFORMATION IS NOT THE SAME |
| PLEASE PROVIDE SPECIFIC DISTANCES |
| REQUIRED BY MANUFACTURE. |
| |
| 5) NOTE: PLEASE VERIFY AIC RATINGS. |
| 702.6,110.9 ETC. |
| |
| 6) NOTE: PLEASE SEE THAT SURVEY/ SITE |
| PLAN SHALL NOT CONTAIN HANDWRITTEN, PEN |
| OR PENCILED PLANS. |
| PLEASE REPRINT AND COPY IF NEEDED. |
| FBC 106.1.2,1.3 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |