2006-11-14 16:21:24 | **** UNSAT ***** |
| |
| **PLEASE SEE RISER(S) HAVE NOW BEEN COMPLETELY REVISED |
| FROM ORIGINAL STAMPED PLANS. PLEASE SEE NEW COMMENTS |
| BELOW BASED ON RISERS NOW SUBMITTED. |
| |
| |
| 1) NOTE: PLEASE SEE SEC?S ARE NOW BEING SHOWN AS #1?S |
| WITH 200A OCP WHICH IS NOT PERMITTED. |
| PLEASE SEE 240.4, 310.16 230.70, 240.20 ETC. |
| |
| 2) NOTE: PLEASE SEE 200A BREAKERS FEEDING 150A RATED |
| PANELS WHICH ARE ALSO NOT PERMITTED. |
| PLEASE SEE THE NEC 230, 240, 408 ETC |
| |
| 3) NOTE: PLEASE SEE RISER WHICH INDICATES AN EQUIPMENT |
| GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS |
| OF DISCONNECT WHICH IS NOT PERMITTED. |
| PLEASE SEE 250.6, 250.24B. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| |
| |
| |
| |