Plan Review Notes
Plan Review Notes For Permit 06070080
Permit Number 06070080
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00***** UNSAT2ND REVIEW ******
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1) NOTE: OK.
  
  
 2) NOTE: NO, PLEASE SEE MISSING A
 DISCONNECTING MEANS FOR FEEDERS FROM
 GEN. THIS CAN BE ON THE LINE SIDE OF ATS
 OR ON THE LOAD SIDE OF THE ATS GROUPED
 WITH EXISTING MAIN. PLEASE SEE THE
 "TOGGLE" SWITCH IS NOT ACCEPATABLE AS A
 DISCONNECTING MEANS. THE DISCONNECT MUST
 BE RATED FOR THE LOAD SERVED AND
 GROUPED. (IT DOES NOT NEED TO CONTAIN
 OCP.)PLEASE SEE 225.31-225.39
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE KNOW,
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN MAY BE REQUIRED IF THE
 SE RATED ATS IS NOT GROUPED WITH THE
 EXISITNG MCB PANEL. PLEASE KNOW THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 IT SEEMS THEY ARE GROUPED BUT UNCLEAR AT
 THIS TIME?
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE:NO, PLEASE SEE THIS ALSO
 INCLUDES THE LOAD CALCULATIONS PAGES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE:OK, REVISED HOWEVER PLEASE SEE
 REVISED SURVEY IS BEING ROUTED TO ZONING
 SO THAT SETBACK NOW REVISED IS STILL OK.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 5) NOTE: PLEASE SEE RISER SHOWS ONLY A
 #8 FROM GEN TO ATS. PLEASE SEE 250.122
 FOR MIN SIZE REQUIRED FOR OCP PROVIDED.
 (# 6 MIN).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]