2006-07-16 00:00:00 | ***** UNSAT ****** |
| |
| 1) NOTE: PLEASE SEE RISER DOES NOT |
| INDICATE THE CONDUCTORS FROM METER TO SE |
| RATED ATS AND FROM ATS TO EXISTING |
| PANEL. |
| PLEASE BE SURE TO ADD EQUIPMENT |
| GROUNDING AFTER THE FIRST MEANS OF |
| DISCONNECT. PLEASE ALSO KNOW, ALL GRNDS |
| AND NEUTRALS WILL BE REQUIRED TO BE |
| SEPARATED IN THE EXISTING MCB PANEL. |
| |
| 2) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL |
| SERVICE EQUIPMENT. PLEASE KNOW, |
| DISCONNECTING MEANS FOR THE FEEDER |
| COMING FROM GEN MAY BE REQUIRED IF THE |
| SE RATED ATS IS NOT GROUPED WITH THE |
| EXISITNG MCB PANEL. PLEASE KNOW THE |
| BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR |
| THE REQUIRED MEANS OF DISCONNECT. |
| IT SEEMS THEY ARE GROUPED BUT UNCLEAR AT |
| THIS TIME? |
| ** THE SE RATED ATS'S ONLY DISCONNECT |
| THE POWER FROM THE NORMAL/FPL SIDE. |
| 225.31-225.39,110.27 ETC. |
| |
| 3) NOTE: PLEASE KNOW, ALL PLANS SHALL |
| BEAR THE PRINTED NAME AND THE SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR |
| PLANS/DESIGN. |
| FBC ADMIN SECT 106.1.2 |
| |
| 4) NOTE: PLEASE KNOW, THE GEN WILL BE |
| REQUIRED TO BE LOCATED A MIN OF 5' FROM |
| THE DWELLING AND ANY OTHER SURROUNDING |
| STRUCTURAL ELEMENTS. |
| PLEASE KNOW, AS PER LETTER OBTAINED FROM |
| GENERAC, THE MIN RECOMMENDED CLEARENCES |
| FOR LIQUID COOLED UNITS IS 5FT. |
| PLEASE SEE THAT MANUFACTURE SPECS |
| SUBMITTED INDICATED THE MIN CLEARENCE. |
| 110.3, |
| ** PLEASE KNOW, THE SITE PLAN WHICH WAS |
| STAMPED BY ZONING WILL NEED TO BE |
| REVISED IF UNIT IS 5FT FROM DWELLING. |
| |
| 5) NOTE: PLEASE SEE RISER SHOWS ONLY A |
| #8 FROM GEN TO ATS. PLEASE SEE 250.122 |
| FOR MIN SIZE REQUIRED FOR OCP PROVIDED. |
| (# 6 MIN). |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |