2006-09-26 00:00:00 | ***** UNSAT 2ND REVIEW ***** |
| |
| ** PLEASE SEE SOME COMMENTS BELOW ARE |
| STILL IN NEED OF ADDRESSING. PLEASE SEE |
| NOTES BELOW WHICH ARE TAKEN DIRECTLY |
| FROM THE PREVIOUS REVIEW WITH NEW NOTES |
| ADDED. |
| |
| |
| |
| 1) NOTE:NO, PLEASE SEE DESIGNATIONS ON |
| PLANS FOR PANELS ARE NOT COMPLETE AND |
| NOT ALL CORRELATE WITH RISER AND PANEL |
| SCHEDULES. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE PLANS, RISER |
| AND PANEL SCHEDULES. |
| PLEASE SEE PLANS SHOWS PANEL R-8, P* AND |
| SEE RISER SHOWS L8A, R8B, AND PANEL |
| SCHEDULE SHOW P8B L8A. |
| 106.1.2 FBC |
| |
| 2) NOTE:OK, HOWEVER STILL NEED TO |
| CORRELATE WITH CHANGES. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE TRANSFORMER FOR |
| EXISTING PANEL NOTED ABOVE COULD NOT BE |
| LOCATED. |
| IF EXISTING, PLEASE ALSO IDENTIFY ON |
| TRANSFORMER SCHEDULE (EVEN IF EXISTING |
| ). |
| 106.1.2 FBC, 90.7 |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE:NO, CODES FOR DESIGN AND |
| PERMITTING OF PROJECT IS REQUIRED ON |
| PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT PLANS REFLECT |
| THE FOLLOWING CODES AT A MIN. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101 |
| |
| 5) NOTE: NO, PLEASE SEE THIS IS FOR ALL |
| SHEETS AND FOR ALL TRADES WHETHER OR |
| NOT COMMENT IS MADE BY OTHER TRADES. |
| PLEASE KNOW, FOR SHEETS WHICH DO NOT |
| NEED CHANGING, THESE MAY SIMPLY BE |
| RESIGNED. |
| |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE HAVE ENGINEER SIGN PLANS |
| WITHHIS RECOGNIZED SIGNATURE AND THAT |
| OF WHICH IS ONFILE WITH THE CITY OF |
| WEST PALM BEACH. |
| |
| 5) NOTE: PLEASE SEE NOTICE WITH RESPECT |
| TO FS 553.80(2)9B)IS ONLY GIVEN AS A |
| NOTICE AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |