Date |
Text |
2006-07-21 00:00:00 | ******* UNSAT ********* |
| |
| 1) NOTE: PLEASE CORRELATE PLANS, RISER |
| AND PANEL SCHEDULES. |
| PLEASE SEE PLANS SHOWS PANEL R-8, P* AND |
| SEE RISER SHOWS L8A, R8B, AND PANEL |
| SCHEDULE SHOW P8B L8A. |
| 106.1.2 FBC |
| |
| 2) NOTE: PLEASE SEE TRANSFORMER FOR |
| EXISTING PANEL NOTED ABOVE COULD NOT BE |
| LOCATED. |
| IF EXISTING, PLEASE ALSO IDENTIFY ON |
| TRANSFORMER SCHEDULE (EVEN IF EXISTING |
| ). |
| 106.1.2 FBC, 90.7 |
| |
| 3) NOTE: PLEASE SEE 240.21 408.16 AS A |
| NOTED ON TRANSFORMER SCHEDULE MENTIONS |
| FOR THE MAINS ON THE PANELS ON THE |
| SECONDARY SIDE OF TRANSFORMER TO BE THE DISCONNECTING |
| MENAS, HOWEVER PLEASE SEE |
| PANELS AS TWO ARE SHOWN AS MLO> |
| |
| 4) NOTE: PLEASE SEE THAT PLANS REFLECT |
| THE FOLLOWING CODES AT A MIN. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101 |
| |
| 5) NOTE: PLEASE HAVE ENGINEER SIGN PLANS |
| WITHHIS RECOGNIZED SIGNATURE AND THAT |
| OF WHICH IS ONFILE WITH THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND BEFORE |
| RESUBMITTING PLANS. PLEASE BE SURE TO |
| COMPLETELY REMOVED ANY OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE ONLY SUBMIT ONE SET OF THE OLD |
| VOIDED SHEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |