Plan Review Notes
Plan Review Notes For Permit 06070059
Permit Number 06070059
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-16 00:00:00****** UNSAT **********
  
 1) NOTE: PLEASE INDICATE THIS SIZE OF
 THE EXISTING DISCONNECT SHOWN ON RISER
 FEEDING THE 125 MLO PANEL. UNABLE TO
 VERIFY CONDUCTORS, OPC ETC.
 240.4,215.5,310.16
  
 2) NOTE: PLEASE PROVIDE PANEL SCHEDULE
 FOR BRANCH CIRCUITS, OCP FOR EACH
 CIRCUIT BEING TAKEN TO 2ND FLR J-BOX.
 PLEASE ALSO KNOW, DERATING FOR THESE
 BRANCH CIRUITS WILL BE REQUIRED FOR
 AMBIENT AIR TEMPS ON OUTSIDE WALL.
 310.16
 PLEASE ALSO SEE THE NUMBER OF CIRCUITS
 IS NOT CLEAR AS THE PRINT OF THE SHEET
 SEEMS TO CUT THIS OFF.
  
 3) NOTE: PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  