Plan Review Notes For Permit 06070059 |
Permit Number |
06070059 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-16 00:00:00 | ****** UNSAT ********** | | | | 1) NOTE: PLEASE INDICATE THIS SIZE OF | | THE EXISTING DISCONNECT SHOWN ON RISER | | FEEDING THE 125 MLO PANEL. UNABLE TO | | VERIFY CONDUCTORS, OPC ETC. | | 240.4,215.5,310.16 | | | | 2) NOTE: PLEASE PROVIDE PANEL SCHEDULE | | FOR BRANCH CIRCUITS, OCP FOR EACH | | CIRCUIT BEING TAKEN TO 2ND FLR J-BOX. | | PLEASE ALSO KNOW, DERATING FOR THESE | | BRANCH CIRUITS WILL BE REQUIRED FOR | | AMBIENT AIR TEMPS ON OUTSIDE WALL. | | 310.16 | | PLEASE ALSO SEE THE NUMBER OF CIRCUITS | | IS NOT CLEAR AS THE PRINT OF THE SHEET | | SEEMS TO CUT THIS OFF. | | | | 3) NOTE: PLEASE KNOW, ALL PLANS SHALL | | BEAR THE PRINTED NAME AND THE SIGNATURE | | OF THE PERSON RESPONSIBLE FOR | | PLANS/DESIGN. | | FBC ADMIN SECT 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|