Plan Review Notes For Permit 06070012 |
Permit Number |
06070012 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-06 00:00:00 | *** PROVISO *** | | 1) DUCTS IN GARAGE NEED TO BE 26 GAGE | | STEEL OR OTHER APPROVED MATERIAL, PER | | 2004 FBC/R 309.1.1, AND NEED TO HAVE R-6 | | INSULATION, PER 2004 FBC 13-610.1.B.1 . | | 2) THE DWELLING WILL BE REQUIRED TO HAVE | | SMOKE ALARMS INSTALLED IF NOT ALREADY | | PRESENT, PER 2004 FBC/R 313.1.1, AND SEE | | 2004 FEBC 303.1 LEVEL ONE ALTERATION | | INCLUDE REPLACEMENT OF EQUIPMENT. | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|