2006-07-10 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW: |
| |
| 1. PER PHONE CONVERSATION ON 7/10/06 |
| WITH R. IRWIN GAS SYSTEM TO BE 0.5 PSI. |
| THE SUBMITTED PRINTS INDICATE A 2LB PSI |
| SYSTEM. NOTE: THE SUBMITTED PRINTS ARE |
| SIGNED AND SEALED BY AN ENGINEER AND ANY |
| CHANGES TO THE PRINT SHALL BE MADE BY |
| THE ENGINEER OF RECORD. |
| 2. NOTE: ANY BELOW GROUND PIPING TO BE |
| COPPER OR OTHER APPROVED MATERIAL PER |
| FBC-2004 FUEL GAS. GALVANIZED PIPING |
| BELOW GROUND SHALL NOT BE USED PER |
| FBC-2004 FUEL GAS, SECTION 404.8. PLEASE |
| INDICATE THE BELOW GROUND MATERIAL TYPE |
| ON THE PRINT FOR RESUBMITTAL. |
| 3. THE POOL HEATER IS SIZED WRONG PER |
| FBC-2004 FUEL GAS, TABLE 402.4(8) PLEASE |
| SEE ATTACHED TABLE FOR REFERENCE FOR |
| RESUBMITTAL |
| 4. PER THE FLORIDA ADMINISTRATIVE CODE |
| THE ENGINEER OF RECORD SHALL: |
| (FAC-61G15-23.002) IF PRACTICING THROUGH |
| A DULY AUTHORIZED ENGINEERING BUSINESS, |
| ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME LICENSE NUMBER, AS WELL AS, THE |
| NAME, ADDRESS, AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGNEERING |
| BUSINESS ON EACH SHEET. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |