Plan Review Notes
Plan Review Notes For Permit 06070010
Permit Number 06070010
Review Stop G
Sequence Number 1
Notes
Date Text
2006-07-10 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW:
  
 1. PER PHONE CONVERSATION ON 7/10/06
 WITH R. IRWIN GAS SYSTEM TO BE 0.5 PSI.
 THE SUBMITTED PRINTS INDICATE A 2LB PSI
 SYSTEM. NOTE: THE SUBMITTED PRINTS ARE
 SIGNED AND SEALED BY AN ENGINEER AND ANY
 CHANGES TO THE PRINT SHALL BE MADE BY
 THE ENGINEER OF RECORD.
 2. NOTE: ANY BELOW GROUND PIPING TO BE
 COPPER OR OTHER APPROVED MATERIAL PER
 FBC-2004 FUEL GAS. GALVANIZED PIPING
 BELOW GROUND SHALL NOT BE USED PER
 FBC-2004 FUEL GAS, SECTION 404.8. PLEASE
 INDICATE THE BELOW GROUND MATERIAL TYPE
 ON THE PRINT FOR RESUBMITTAL.
 3. THE POOL HEATER IS SIZED WRONG PER
 FBC-2004 FUEL GAS, TABLE 402.4(8) PLEASE
 SEE ATTACHED TABLE FOR REFERENCE FOR
 RESUBMITTAL
 4. PER THE FLORIDA ADMINISTRATIVE CODE
 THE ENGINEER OF RECORD SHALL:
 (FAC-61G15-23.002) IF PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGNEERING
 BUSINESS ON EACH SHEET.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  