Plan Review Notes For Permit 06061717 |
Permit Number |
06061717 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-12-31 16:02:46 | ** REDLINED NOTES ** | | | | | | 1) MCB ON THE SECONDARY SIDE OF THE TRANSFORMER SHALL | | BE INSTALLED WITHIN 25FT OF CONDUCTORS MAX PER | | 240.21C. | | OCP TO BE PER PLANS, 200A MAX. | | 2) THE GENERATOR CHANGE OUT/UPGRADE SHALL BE COMPLETED | | BEFORE FINAL ON THIS PERMIT CAN BE GRANTED. | | | | | | *** OWES $1,210 FOR INCREASED VALUE. MUST BE PAID | | BEFORE PERMIT CAN PRINT. |
|