Date |
Text |
2006-10-04 00:00:00 | **** PLEASE SEE 300.19A FOR SIZE AND |
| LENGTH OF CONDUCTORS. |
| SUPPORTS WHICH WOULD REQUIRE SOME TYPE |
| OF PULL BOXES, WOULD NOT BE PERMITTED IN |
| STAIRTOWERS. |
2006-09-18 00:00:00 | **** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| REVIEW AND SOME NEW NOTES DUE TO |
| INFORMATION ON PLANS. |
| PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECLTY FROM PREVIOUS REVIEW WITH NEW |
| NOTES ADDED AT THE BOTTOM. |
| |
| |
| |
| |
| 1) NOTE: NO, EXISTING RISER, OCP, SIZE |
| ETC STILL NEEDS TO BE SHOWN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CLARIFY AND SPECIFY THE |
| TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW |
| PROPOSED CONNECTION IS COMING FROM. |
| PLEASE KNOW, AS SHOWN THIS MAY NOT BE |
| TAPPED FROM THE EXISTING EM DIST SYSTEM. |
| PLEASE KNOW THERE IS MUCH INFORMATION |
| NOT SUBMITTED FOR CONSIDERATION TO DO |
| SO. |
| 700,701,NFPA-110CHAPTERS 5,6,7. |
| |
| 2) NOTE:NO, PLEASE SEE DETAIL AS SHOWN |
| FOR STAIRS IS STILL IN QUESTION, AND |
| CONFORMATION WITH THE BUILDING REVIEW |
| APPEARS THE SIZE OF REQUESTED ENCLOSURE |
| IS TOO LARGE IN STAIRS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE BUILDING AND FIRE |
| REVIEW COMMENTS, AS CONDUITS SHOWN ARE |
| BEING PROPOSED IN THE STAIR WAYS WHICH |
| ARE NOT PERMITTED. NO EXCEPTIONS. |
| |
| 3) NOTE:NO, PLEASE KNOW THAT NO |
| VERIFICATION OF EXISTING CAN BE DONE AS |
| THE PERMITTING , INSTALLATION AND |
| UPGRADE FOR EXISTING OLD GENERATOR IS |
| NOT YET DONE. |
| ** PLEASE SEE NOTE WHICH MENTIONS "KEMM" |
| CONSULTING.? PLEASE VERIFY ,AS THIS MAY |
| BE A MISPRINT FOR NAME. |
| PLEASE KNOW, AS THESE ARE NOW PART OF A |
| LEGALLY REQUIRED SYSTEM, SIZING , |
| LOCATION ETC MUST BE VERIFIED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| |
| PLEASE PROVIDE LOAD |
| CALCULATIONS FOR ALL PROPOSED LOADS |
| BEING ADDED TO EXISTING LOADS. |
| DEPENDING ON THE CONNECTIONS OF THE EM |
| DIST SYSTEM AND TRANSFER DEVICES ETC, IT |
| IS KNOWN TO THIS OFFICE THAT THIS |
| BUILDING (MARRIOTT HOTEL) IS CURRENTLY |
| PROPOSING THE INSTALLATION OF A NEW EM |
| GEN AND DIST SYSTEM WHICH IS NOT YET |
| PERMITTED. |
| PLEASE KNOW, COMPLETE LOAD CALCS AND/OR |
| DEMANDS AND NEW LOADS ARE REQUIRED AT |
| THIS TIME. THERE WILL BE NO EXCEPTIONS |
| OR "PROVISOS" (CONDITION TO ISSUE) |
| GRANTED. |
| 220, 215.5, ETC |
| 106.1.2 FBC ADMIN SECT |
| |
| 4) NOTE: NO, PLEASE SEE PLANS STILL |
| INDICATE THE 2005. THIS WAS REDLINED AND |
| HIGHLIGHTED ON PLANS. |
| |
| ** PREVIOUS REVIEW NTOE ** |
| PLEASE SEE PLANS CURRENTLY CALL |
| FOR THE 2005 NEC. PLEASE KNOW, THE STATE |
| OF FLORIDA IS STILL CURRENTLY UNDER |
| UNDER THE 2002 NFPA-70 |
| |
| 5) NOTE: NO?? THIS IS IN QUESTION , AS |
| ALL EQUIPMENT BEING SHOWN ON PLANS AND |
| LABOUR FOR INSTALLATION SEEMS TO BE |
| HIGHER THAN SHOWN ON APPLICATION. |
| SIGNED, DATED AND NOTARIZED CONTRACT(S) |
| ARE REQUIRED. FBC 108.3. |
| THIS SCOPE IS FOR ALL ELECTRICAL , |
| BUILDING, MECHANICALETC. |
| |
| ** PLEASE SEE VALUE SHALL BE BASED |
| ON ALL LABOR AND MATERIALS, EVEN IF ANY |
| OF THE EQUIPMENT OR MATERIALS ARE OWNER |
| SUPPLIED. PLEASE KNOW, IF VALUE IS NOT |
| ADJUSTED, ONE WILL BE ASSESSED BY THIS |
| OFFICE USING GUIDES AS ADOPTED INTO THE |
| FBC. 108.3 ADMIN SETC. |
| |
| 6) NOTE: NO, PLEASE SEE SOME NOTES SHOWN |
| ON SHEETS DO NOT CORRELATE WITH "CODED |
| NOTES", PLEASE SEE UNABLE TO VERIFY SOME |
| ITEMS. |
| 240.21, PANEL ON SECONDARY SIDE OF THE |
| TRANSFORMER ETC. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE COMPLETE PLANS , NOTES |
| AND RISER. PLEASE SEE THERE ARE |
| NUMERICAL NOTES ON PLANS WHICH ARE SHOWN |
| SHOWN ON NOTES.. PLEASE PLACE NOTES AND |
| INFORMATION ON RISER. THIS WILL HELP THE |
| REVIEW PROCESS OF JUMPING BACK AND FORTH |
| FROM PAGES. PLEASE SEE NOTES ONLY GO |
| THROUGH 24. |
| 106.1.2.,90.7 |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: OK. |
| |
| PLEASE SEE COMMENTS FROM OTHER |
| REVIEWER(S). |
| |
| 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT CODE COMPLIANT |
| COMMENTS. THIS IS ONLY NOTED AT THIS |
| TIME. |
| |
| ** IMPORTANT** |
| |
| ONCE ALL REVIEWS ARE DONE, PLANS ARE |
| PICKED UP AND BEFORE RESUBMITTING. |
| PLEASE COMPLETELY REMOVED ALL OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| ONLY ONE COPY OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED BACK FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |