Plan Review Notes
Plan Review Notes For Permit 06061717
Permit Number 06061717
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-04 00:00:00**** PLEASE SEE 300.19A FOR SIZE AND
 LENGTH OF CONDUCTORS.
 SUPPORTS WHICH WOULD REQUIRE SOME TYPE
 OF PULL BOXES, WOULD NOT BE PERMITTED IN
 STAIRTOWERS.
2006-09-18 00:00:00**** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO
 INFORMATION ON PLANS.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECLTY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED AT THE BOTTOM.
  
  
  
  
 1) NOTE: NO, EXISTING RISER, OCP, SIZE
 ETC STILL NEEDS TO BE SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY AND SPECIFY THE
 TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW
 PROPOSED CONNECTION IS COMING FROM.
 PLEASE KNOW, AS SHOWN THIS MAY NOT BE
 TAPPED FROM THE EXISTING EM DIST SYSTEM.
 PLEASE KNOW THERE IS MUCH INFORMATION
 NOT SUBMITTED FOR CONSIDERATION TO DO
 SO.
 700,701,NFPA-110CHAPTERS 5,6,7.
  
 2) NOTE:NO, PLEASE SEE DETAIL AS SHOWN
 FOR STAIRS IS STILL IN QUESTION, AND
 CONFORMATION WITH THE BUILDING REVIEW
 APPEARS THE SIZE OF REQUESTED ENCLOSURE
 IS TOO LARGE IN STAIRS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BUILDING AND FIRE
 REVIEW COMMENTS, AS CONDUITS SHOWN ARE
 BEING PROPOSED IN THE STAIR WAYS WHICH
 ARE NOT PERMITTED. NO EXCEPTIONS.
  
 3) NOTE:NO, PLEASE KNOW THAT NO
 VERIFICATION OF EXISTING CAN BE DONE AS
 THE PERMITTING , INSTALLATION AND
 UPGRADE FOR EXISTING OLD GENERATOR IS
 NOT YET DONE.
 ** PLEASE SEE NOTE WHICH MENTIONS "KEMM"
 CONSULTING.? PLEASE VERIFY ,AS THIS MAY
 BE A MISPRINT FOR NAME.
 PLEASE KNOW, AS THESE ARE NOW PART OF A
 LEGALLY REQUIRED SYSTEM, SIZING ,
 LOCATION ETC MUST BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
  
 PLEASE PROVIDE LOAD
 CALCULATIONS FOR ALL PROPOSED LOADS
 BEING ADDED TO EXISTING LOADS.
 DEPENDING ON THE CONNECTIONS OF THE EM
 DIST SYSTEM AND TRANSFER DEVICES ETC, IT
 IS KNOWN TO THIS OFFICE THAT THIS
 BUILDING (MARRIOTT HOTEL) IS CURRENTLY
 PROPOSING THE INSTALLATION OF A NEW EM
 GEN AND DIST SYSTEM WHICH IS NOT YET
 PERMITTED.
 PLEASE KNOW, COMPLETE LOAD CALCS AND/OR
 DEMANDS AND NEW LOADS ARE REQUIRED AT
 THIS TIME. THERE WILL BE NO EXCEPTIONS
 OR "PROVISOS" (CONDITION TO ISSUE)
 GRANTED.
 220, 215.5, ETC
 106.1.2 FBC ADMIN SECT
  
 4) NOTE: NO, PLEASE SEE PLANS STILL
 INDICATE THE 2005. THIS WAS REDLINED AND
 HIGHLIGHTED ON PLANS.
  
 ** PREVIOUS REVIEW NTOE **
 PLEASE SEE PLANS CURRENTLY CALL
 FOR THE 2005 NEC. PLEASE KNOW, THE STATE
 OF FLORIDA IS STILL CURRENTLY UNDER
 UNDER THE 2002 NFPA-70
  
 5) NOTE: NO?? THIS IS IN QUESTION , AS
 ALL EQUIPMENT BEING SHOWN ON PLANS AND
 LABOUR FOR INSTALLATION SEEMS TO BE
 HIGHER THAN SHOWN ON APPLICATION.
 SIGNED, DATED AND NOTARIZED CONTRACT(S)
 ARE REQUIRED. FBC 108.3.
 THIS SCOPE IS FOR ALL ELECTRICAL ,
 BUILDING, MECHANICALETC.
  
 ** PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOR AND MATERIALS, EVEN IF ANY
 OF THE EQUIPMENT OR MATERIALS ARE OWNER
 SUPPLIED. PLEASE KNOW, IF VALUE IS NOT
 ADJUSTED, ONE WILL BE ASSESSED BY THIS
 OFFICE USING GUIDES AS ADOPTED INTO THE
 FBC. 108.3 ADMIN SETC.
  
 6) NOTE: NO, PLEASE SEE SOME NOTES SHOWN
 ON SHEETS DO NOT CORRELATE WITH "CODED
 NOTES", PLEASE SEE UNABLE TO VERIFY SOME
 ITEMS.
 240.21, PANEL ON SECONDARY SIDE OF THE
 TRANSFORMER ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE COMPLETE PLANS , NOTES
 AND RISER. PLEASE SEE THERE ARE
 NUMERICAL NOTES ON PLANS WHICH ARE SHOWN
 SHOWN ON NOTES.. PLEASE PLACE NOTES AND
 INFORMATION ON RISER. THIS WILL HELP THE
 REVIEW PROCESS OF JUMPING BACK AND FORTH
 FROM PAGES. PLEASE SEE NOTES ONLY GO
 THROUGH 24.
 106.1.2.,90.7
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S).
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS. THIS IS ONLY NOTED AT THIS
 TIME.
  
 ** IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING.
 PLEASE COMPLETELY REMOVED ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED BACK FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]