2006-10-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061717
 ADD: 1001 OKEECHOBEE BLVD
 CONT: CHA TECH SERVICES, LLC
 TEL: (770)286-7297
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMMENT# 7 FROM THE PREVIOUS REVIEW
 DEALS WITH THE CONDUITS IN THE
 STAIRWELL, THAT ARE ENCASED IN A 2
 LAYERS OF ROCK, 1" FIRECORE C CORE PANEL
 AND 1/2" DRYWALL. PLEASE PROVIDE THE
 LISTING FOR A 2 HR ASSEMBLY. 703.2
 FIRE-RESISTANCE RATINGS.
  
 THE SECOND ISSUE IS THE LOCATION OF
 THIS ASSEMBLY IN THE STAIRWELL. 1009.4
 STAIRWAY LANDINGS. THERE SHALL BE A
 FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE WIDTH OF LANDINGS
 SHALL NOT BE LESS THAN THE WIDTH OF
 STAIRWAYS THEY SERVE. EVERY LANDING
 SHALL HAVE A MINIMUM DIMENSION MEASURED
 IN THE DIRECTION OF TRAVEL EQUAL TO THE
 WIDTH OF THE STAIRWAY. SUCH DIMENSION
 NEED NOT EXCEED 48 INCHES (1219 MM)
 WHERE THE STAIRWAY HAS A STRAIGHT RUN.
 E07 INDICATES THAT THE SHAFT
 ENCLOSURE WILL BE 8" AWAY FROM THE WALL
 BUT THE LENGTH IN NOTE# 1 IS AS NEEDED.
 THIS COULD BE ACROSS THE WHOLE LANDING.
 1009.4 STATES THE WIDTH OF LANDINGS
 SHALL NOT BE LESS THAN THE WIDTH OF THE
 STAIRWAYS THEY SERVE.
  
 THE THIRD ISSUE IS LOCATED ON E01 NOTE
 NUMBER 24, JUNCTION BOX SIZE AS REQUIRED
 BY THE NEC. THE ELECTRICAL PLAN REVIEWER
  
 MAY COMMENT ON THIS ISSUE. THERE CAN BE
 NO JUNCTION BOXES THAT WILL COMMUNICATE
 WITHIN THE STAIR TOWER. SEE ORIGINAL
 COMMENT 1019.2 PENETRATIONS INTO AND
 OPENINGS THROUGH AN EXIT ENCLOSURE.
 BUILDING PLAN REVIEW