Plan Review Notes
Plan Review Notes For Permit 06061717
Permit Number 06061717
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00***DENIED***
  
 1) ALL EQUIPMENT INSTALLATIONS SHALL NOT
 INTERFERE WITH FIRE PROTECTION EQUIPMENT
 INSIDE BUILDING OR ON ROOF.
  
 2) NO EQUIPMENT WILL BE ALLOWED INSIDE
 OF STAIRWELLS. PLEASE SEE NFPA 101, 2003
 EDITION SEC. 7.1.3.2.1.(6).
  
 3) PLEASE INDICATE SPECIFIC NFPA CODES
 THAT WILL BE COMPLIED WITH AS STATED ON
 M0.1, NOTE 10. PLEASE INCLUDE
 APPROPRIATE EDITIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  