2006-07-21 00:00:00 | ************ UNSAT **************** |
| |
| ** PLEASE SEE THE FOLLOWING COMMENTS AS |
| THE DESIGN AS SHOWN WILL NOT BE |
| PERMITTED AND CHANGES WILL BE REQUIRED. |
| |
| 1) NOTE: PLEASE CLARIFY AND SPECIFY THE |
| TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW |
| PROPOSED CONNECTION IS COMING FROM. |
| PLEASE KNOW, AS SHOWN THIS MAY NOT BE |
| TAPPED FROM THE EXISTING EM DIST SYSTEM. |
| PLEASE KNOW THERE IS MUCH INFORMATION |
| NOT SUBMITTED FOR CONSIDERATION TO DO |
| SO. |
| 700,701,NFPA-110CHAPTERS 5,6,7. |
| |
| 2) NOTE: PLEASE SEE BUILDING AND FIRE |
| REVIEW COMMENTS, AS CONDUITS SHOWN ARE |
| BEING PROPOSED IN THE STAIR WAYS WHICH |
| ARE NOT PERMITTED. NO EXCEPTIONS. |
| |
| 3) NOTE: PLEASE PROVIDE LOAD |
| CALCULATIONS FOR ALL PROPOSED LOADS |
| BEING ADDED TO EXISTING LOADS. |
| DEPENDING ON THE CONNECTIONS OF THE EM |
| DIST SYSTEM AND TRANSFER DEVICES ETC, IT |
| IS KNOWN TO THIS OFFICE THAT THIS |
| BUILDING (MARRIOTT HOTEL) IS CURRENTLY |
| PROPOSING THE INSTALLATION OF A NEW EM |
| GEN AND DIST SYSTEM WHICH IS NOT YET |
| PERMITTED. |
| PLEASE KNOW, COMPLETE LOAD CALCS AND/OR |
| DEMANDS AND NEW LOADS ARE REQUIRED AT |
| THIS TIME. THERE WILL BE NO EXCEPTIONS |
| OR "PROVISOS" (CONDITION TO ISSUE) |
| GRANTED. |
| 220, 215.5, ETC |
| 106.1.2 FCB ADMIN SECT |
| |
| 4) NOTE: PLEASE SEE PLANS CURRENTLY CALL |
| FOR THE 2005 NEC. PLEASE KNOW, THE STATE |
| OF FLORIDA IS STILL CURRENTLY UNDER |
| UNDER THE 2002 NFPA-70 |
| |
| 5) NOTE: PLEASE SEE VALUE SHALL BE BASED |
| ON ALL LABOR AND MATERIALS, EVEN IF ANY |
| OF THE EQUIPMENT OR MATERIALS ARE OWNER |
| SUPPLIED. PLEASE KNOW, IF VALUE IS NOT |
| ADJUSTED, ONE WILL BE ASSESSED BY THIS |
| OFFICE USING GUIDES AS ADOPTED INTO THE |
| FBC. 108.3 ADMIN SETC. |
| |
| 6) NOTE: PLEASE COMPLETE PLANS , NOTES |
| AND RISER. PLEASE SEE THERE ARE |
| NUMERICAL NOTES ON PLANS WHICH ARE SHOWN |
| SHOWN ON NOTES.. PLEASE PLACE NOTES AND |
| INFORMATION ON RISER. THIS WILL HELP THE |
| REVIEW PROCESS OF JUMPING BACK AND FORTH |
| FROM PAGES. PLEASE SEE NOTES ONLY GO |
| THROUGH 24. |
| 106.1.2.,90.7 |
| |
| 7) NOTE: PLEASE CLARIFY TITLE BLOCKS AS |
| ADDRESSING INFORMATION FOR SAID ENGINEER |
| AND FIRM DO NOT SEEM TO CORRELATE WITH |
| THE STATE'S WEBSITE. PLEASE SEE ATTACHED |
| COPIES PRINTED FROM THE DEPARTMENT OF |
| BUSINESS AND PROFESSIONAL REGULATION. |
| FAC 61G15-23.002, FS 471 |
| |
| 8) NOTE: PLEASE SEE LOCATION OF PROJECT |
| IS NOTED AS "PB MARKETPLACE"?? THIS |
| BUIDLING IS THE MARRIOTT HOTEL. PLEASE |
| ADJUST TITLE BLOCKS. |
| FAC 61G15-23.002 |
| |
| PLEASE SEE COMMENTS FROM OTHER |
| REVIEWER(S). |
| |
| ** IMPORTANT** |
| |
| ONCE ALL REVIEWS ARE DONE, PLANS ARE |
| PICKED UP AND BEFORE RESUBMITTING. |
| PLEASE COMPLETELY REMOVED ALL OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| ONLY ONE COPY OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED BACK FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |