Plan Review Notes
Plan Review Notes For Permit 06061717
Permit Number 06061717
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-21 00:00:00************ UNSAT ****************
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 THE DESIGN AS SHOWN WILL NOT BE
 PERMITTED AND CHANGES WILL BE REQUIRED.
  
 1) NOTE: PLEASE CLARIFY AND SPECIFY THE
 TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW
 PROPOSED CONNECTION IS COMING FROM.
 PLEASE KNOW, AS SHOWN THIS MAY NOT BE
 TAPPED FROM THE EXISTING EM DIST SYSTEM.
 PLEASE KNOW THERE IS MUCH INFORMATION
 NOT SUBMITTED FOR CONSIDERATION TO DO
 SO.
 700,701,NFPA-110CHAPTERS 5,6,7.
  
 2) NOTE: PLEASE SEE BUILDING AND FIRE
 REVIEW COMMENTS, AS CONDUITS SHOWN ARE
 BEING PROPOSED IN THE STAIR WAYS WHICH
 ARE NOT PERMITTED. NO EXCEPTIONS.
  
 3) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS FOR ALL PROPOSED LOADS
 BEING ADDED TO EXISTING LOADS.
 DEPENDING ON THE CONNECTIONS OF THE EM
 DIST SYSTEM AND TRANSFER DEVICES ETC, IT
 IS KNOWN TO THIS OFFICE THAT THIS
 BUILDING (MARRIOTT HOTEL) IS CURRENTLY
 PROPOSING THE INSTALLATION OF A NEW EM
 GEN AND DIST SYSTEM WHICH IS NOT YET
 PERMITTED.
 PLEASE KNOW, COMPLETE LOAD CALCS AND/OR
 DEMANDS AND NEW LOADS ARE REQUIRED AT
 THIS TIME. THERE WILL BE NO EXCEPTIONS
 OR "PROVISOS" (CONDITION TO ISSUE)
 GRANTED.
 220, 215.5, ETC
 106.1.2 FCB ADMIN SECT
  
 4) NOTE: PLEASE SEE PLANS CURRENTLY CALL
 FOR THE 2005 NEC. PLEASE KNOW, THE STATE
 OF FLORIDA IS STILL CURRENTLY UNDER
 UNDER THE 2002 NFPA-70
  
 5) NOTE: PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOR AND MATERIALS, EVEN IF ANY
 OF THE EQUIPMENT OR MATERIALS ARE OWNER
 SUPPLIED. PLEASE KNOW, IF VALUE IS NOT
 ADJUSTED, ONE WILL BE ASSESSED BY THIS
 OFFICE USING GUIDES AS ADOPTED INTO THE
 FBC. 108.3 ADMIN SETC.
  
 6) NOTE: PLEASE COMPLETE PLANS , NOTES
 AND RISER. PLEASE SEE THERE ARE
 NUMERICAL NOTES ON PLANS WHICH ARE SHOWN
 SHOWN ON NOTES.. PLEASE PLACE NOTES AND
 INFORMATION ON RISER. THIS WILL HELP THE
 REVIEW PROCESS OF JUMPING BACK AND FORTH
 FROM PAGES. PLEASE SEE NOTES ONLY GO
 THROUGH 24.
 106.1.2.,90.7
  
 7) NOTE: PLEASE CLARIFY TITLE BLOCKS AS
 ADDRESSING INFORMATION FOR SAID ENGINEER
 AND FIRM DO NOT SEEM TO CORRELATE WITH
 THE STATE'S WEBSITE. PLEASE SEE ATTACHED
 COPIES PRINTED FROM THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 FAC 61G15-23.002, FS 471
  
 8) NOTE: PLEASE SEE LOCATION OF PROJECT
 IS NOTED AS "PB MARKETPLACE"?? THIS
 BUIDLING IS THE MARRIOTT HOTEL. PLEASE
 ADJUST TITLE BLOCKS.
 FAC 61G15-23.002
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S).
  
 ** IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING.
 PLEASE COMPLETELY REMOVED ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED BACK FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]