2006-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061717
 ADD: 1001 OKEECHOBEE BLVD
 CONT: CHA TECH SERVICES, LLC
 TEL: (770)286-7297
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) CHA, CLOUGH HARBOUR & ASSOCIATESLLP
 PLEASE PROVIDE THE ADDRESS AS STATED
 UNDER THE CERTIFICATE OF AUTHORIZATION
 FILED WITH THE STATE. IF THIS LOCATION
 IS A SECOND OFFICE THE OFFICE REGISTERED
 WITH STATE IS REQUIRED, THIS SECONDARY
 ADDRESS THEN MAY BE INCLUDED.
  
 4) THE TITLE BLOCK LIST PB MARKETPLACE
 AS THE LOCATION FOR THE JOB? THIS
 ADDRESS IS FOR THE "MARRIOT".PLEASE
 CORRECT THE TITLE BLOCK. 61G15-23.002.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. LEVEL OF
 ALTERATION EXISTING BUILDING CODE.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 6) SHEET CO4 DETAIL# 5 FOR WALL AND
 CEILING, PLANS INDICATE THAT UL LISTING
 U-334 WILL BE USED. PLANS INDICATE A 2
 HR RATED WALL WHEREAS THE DETAIL
 INDICATES ONLY ONE LAYER OF 5/8" DRYWALL
 BUT THE UL LISTING REQUIRES 2 LAYERS.
 THE OTHER ISSUE IS THE LISTING INDICATES
 THE USE OF WOOD STUDS FOR A BEARING
 WALL. IS THIS TO BE USED AS A BEARING
 WALL.? THE OTHER ISSUE IS WOOD STUDS
 BEING USED IN A TYPE 1A BUILDING.
 WILL THERE BE FIRE SPRINKLERS ADDED TO
 THIS SPACE OR A DRY SYSTEM (HALON)?
  
 7) SHEET E01 INDICATES CONDUITS TO BE
 INSTALLED IN THE STAIR TOWER.1019.1.2
 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT
 ENCLOSURES.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026