2006-08-08 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06061717 |
| ADD: 1001 OKEECHOBEE BLVD |
| CONT: CHA TECH SERVICES, LLC |
| TEL: (770)286-7297 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) CHA, CLOUGH HARBOUR & ASSOCIATESLLP |
| PLEASE PROVIDE THE ADDRESS AS STATED |
| UNDER THE CERTIFICATE OF AUTHORIZATION |
| FILED WITH THE STATE. IF THIS LOCATION |
| IS A SECOND OFFICE THE OFFICE REGISTERED |
| WITH STATE IS REQUIRED, THIS SECONDARY |
| ADDRESS THEN MAY BE INCLUDED. |
| |
| 4) THE TITLE BLOCK LIST PB MARKETPLACE |
| AS THE LOCATION FOR THE JOB? THIS |
| ADDRESS IS FOR THE "MARRIOT".PLEASE |
| CORRECT THE TITLE BLOCK. 61G15-23.002. |
| |
| 5) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. LEVEL OF |
| ALTERATION EXISTING BUILDING CODE. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| |
| 6) SHEET CO4 DETAIL# 5 FOR WALL AND |
| CEILING, PLANS INDICATE THAT UL LISTING |
| U-334 WILL BE USED. PLANS INDICATE A 2 |
| HR RATED WALL WHEREAS THE DETAIL |
| INDICATES ONLY ONE LAYER OF 5/8" DRYWALL |
| BUT THE UL LISTING REQUIRES 2 LAYERS. |
| THE OTHER ISSUE IS THE LISTING INDICATES |
| THE USE OF WOOD STUDS FOR A BEARING |
| WALL. IS THIS TO BE USED AS A BEARING |
| WALL.? THE OTHER ISSUE IS WOOD STUDS |
| BEING USED IN A TYPE 1A BUILDING. |
| WILL THERE BE FIRE SPRINKLERS ADDED TO |
| THIS SPACE OR A DRY SYSTEM (HALON)? |
| |
| 7) SHEET E01 INDICATES CONDUITS TO BE |
| INSTALLED IN THE STAIR TOWER.1019.1.2 |
| PENETRATIONS. |
| PENETRATIONS INTO AND OPENINGS THROUGH |
| AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT |
| FOR REQUIRED EXIT DOORS, EQUIPMENT AND |
| DUCTWORK NECESSARY FOR INDEPENDENT |
| PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE |
| DEPARTMENT COMMUNICATION AND ELECTRICAL |
| RACEWAY SERVING THE EXIT ENCLOSURE AND |
| TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M 2 ). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN |
| ACCORDANCE WITH SECTION 712 . THERE |
| SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT |
| ENCLOSURES. |