Date |
Text |
2006-09-24 00:00:00 | ******** UNSAT 2ND REVIEW ************ |
| |
| ** PLEASE SEE MOST NOTES FROM PREVIOUS |
| REVIEW STILL APPLY ALONG WITH SOME NEW |
| COMMENTS DUE TO CHANGES IN PLANS. |
| **PLEASE SEE THE EXACT SAME PLANS WERE |
| SUBMITTED BACK WITH OUT CODE CORRECTIONS |
| BEING MADE.?? |
| |
| 1) NOTE:NO, A VALUE WAS CHANGED ON |
| APPLICATIONWAS INCREASED TO $55K, |
| HOWEVER THIS VALUE IS WAY LOW. PLEASE |
| KNOW, IF THIS IS NOT ADJUSTED |
| APPROPRIATLY, ONE WILL BE ASSESSED BASED |
| ON THE MARSHALLS & SWIFT GUIDE AND |
| TODAYS CURRENT RATES ADOPTED INTO TEH |
| FBC. 108.3. |
| THE VALUE ON THE GENERATO ALONE IS |
| HIGHER THAN THAT GIVEN, WHICH DOES NOT |
| INCLUDE THE $10K+ ATS, , SLAB, AND |
| LABOUR. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE VALUE FOR |
| COMPLETE SCOPE OF WORK SHALL BE |
| INLCUDED. PLEASE KNOW, EVEN IF ANY |
| EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3 , ADMIN SECT. |
| PLEASE ADJUSTOR ONE WILL BE ASSESSED |
| PER MARSHALL'S SWIFT GUIDE AS ADOPTED |
| UNDER THE FBC. |
| |
| 2) NOTE: SUBMITTED, HOWEVER THIS WILL BE |
| REVIEWED BY BUILDING. PLEASE SEE THAT |
| THE ELEVATIONS FOR THIS MUST BE A MINOF |
| 6" ABOVE BFE. THIS IS NOT YET INDICATED |
| ON PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE SLAB INFORMATION |
| AT THIS TIME. PLEASE KNOW, THE SIZE, TIE |
| DOWN ETC FOR GEN AND SLAB INFORMATION IS |
| REQUIRED AT THIS TIME BEFORE PERMIT FOR |
| GENERATOR CAN BE ISSUED. |
| PLEASE SEE BUIDLING REVIEW COMMENTS. |
| 106.1.2 |
| |
| 3) NOTE:NO, SAME NOTE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE AND CLARIFY |
| ATS BEING INSTALLED. NO |
| SPES/MANUFCATURES CUT SHEETS WERE |
| SUBMITTED FOR REVIEW. PLEASE SEE A PRINT |
| OUT FROM AN WEBSITE INDICATE AN "ONAN" |
| YET PLANS CALL FOR GENERAC ATS WHICH |
| WOULD CORRELATE WITH THE LISTED GENERAC |
| GENERATOR. |
| PLEASE CORRELATE AND SUBMIT ALL |
| INFORMATION. |
| PLEASE SEE MISSING WP HOUSING SPECS. |
| PLEASE BE SURE MIN CLEARENCES ARE |
| INDICATE FOR GEN AND PLEASE BE SURE AIC |
| RATINGS FOR ALL EQUIPMENT IS SHOWN. |
| 110.9,702.6,215.5,110.26,110.3,90.7 ETC |
| |
| 4) NOTE: NO, SEEMS TO BE SUBMITTED, |
| HOWEVER LISTINGS TO BE VERIFIED. |
| PLEASE SEE NO CALCULATIONS WERE |
| SUBMITTED FOR FUEL USESAGE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT THE SPECS/CUT |
| SHEET FOR FUEL TANK AND SIZE. PLEASE |
| INDICATE GPH USESAGE AND SHOW ON PLANS. |
| PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT |
| WILL BE SEPARATE THIS INFORMATION IS |
| REQUIRED AT THIS TIME. PLEASE ALSO SEE |
| MECH REVIEW AND FIRE REVIEW COMMENTS. |
| 110.3,90.7, |
| 106.1.2 FBC |
| |
| 5) NOTE: NO, SAME NOTE> |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SPECIFY THE NFPA-110 |
| PLEASE SEE CHAPTER 27 OF THE 2004 FBC, |
| AND 2002 110. |
| |
| 6) NOTE: NO, THIS WAS DONE, HOWEVER THIS |
| INFORMATION WAS HANDWRITTEN ON PLANS |
| WHICH IS NOT PERMITTED. PLEASE BES URE |
| THE ENGINEER OF RECORD MAKES THE |
| REQUIRED CHANGES. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SHOW AND INDICATE ALL |
| SETBACKS FOR GENERATOR AND EQUIPMENT. |
| 106.1.2 |
| |
| 7) NOTE:NO, SAME NOTE. NOT ENNOUGH |
| INFORMATION SUBMITTED FOR COMPLETE |
| REVIEW AND CODE COMPLIANCE IS NOT YET |
| MET. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CLARIFY IF THE EXISTING |
| MAIN PANEL WHERE IT APPEARS TO BE |
| LOCATED ADJACENT TO THE NEW SE RATED ATS |
| CONTAINS A MAIN? |
| PLEASE ALSO PROVIDE INFORMATION BY THE |
| WAY OF THE SPECS TO BE SUBMITTED AND |
| PLANS THAT THE ATS CONTAINS A MANUAL |
| MEANS OF DISCONNECT RATED FOR THE LOAD |
| SERVED ON THE OUTSIDE AS REQUIRED PER |
| 230.70,230.76,230.79. |
| PLEASE KNOW, IF THE EXISTING MAIN PANEL |
| DOES NOT CONTAIN MCB, AND THE ATS DOES |
| NOT DISCONNECT POWER FROM BOTH NORMAL |
| AND EM SIDES TO A CENTER OFF POSITION, A |
| MEANS OF DISCONNECT WILL BE REQUIRED |
| LOCATED AT BUIDLING GROUPED WITH OUTHER |
| MAINS. |
| 225.31-225.39, 230.72, 230.70 |
| |
| |
| ** NEW NOTRES** |
| |
| 8) NOTE: PLEASE SEE ONLY ONE SET OF |
| PLANS ARE SIGNED, DATED AND SEALED. |
| PLEASE SEE FAC 61G15-23.002, FS 471.025. |
| |
| 9) NOTE: PLEASE SEE AS THE SAME PLANS |
| ORIGINAL SUBMITTED WERE BROUGHT BACK |
| WITH HAND DRAWN CHANGES ON SOME SHEETS, |
| AND NOT CORRECTIONS MADE, ONE SET OF |
| PLANS ARE BEING RETAINED FOR FILE FOR |
| POSSIBLE REVIEW BY THE FBPE'S. |
| PLEASE SEE FS 553.80(2)(B) WITH RESPECT |
| TO REPEAT CODE COMPLIANT COMMENTS FOR |
| DESIGN PREOFESSIONALS. |
| |
| 10) NOTE: PLEASE SEE THE NOTICE OF |
| COMMENCMENT SUBMITTED IS NO LONGER VALID |
| AND IS NULL AND VOID. PLEASE SEE FS |
| 713.13(2). WHEN WORK HAS NOT COMMENCED |
| WITHIN 90 DAYS OF RECORDING SUCH NOC, |
| THEN THE DOCUMENT OF VOID> |
| ** THE RECORDED NOC IS ONLY REQUIRED |
| WHEN PICKING UP PERMIT. |
| |
| |
| PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL AND OTHER |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |