2006-09-24 00:00:00******** UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE MOST NOTES FROM PREVIOUS
 REVIEW STILL APPLY ALONG WITH SOME NEW
 COMMENTS DUE TO CHANGES IN PLANS.
 **PLEASE SEE THE EXACT SAME PLANS WERE
 SUBMITTED BACK WITH OUT CODE CORRECTIONS
 BEING MADE.??
  
 1) NOTE:NO, A VALUE WAS CHANGED ON
 APPLICATIONWAS INCREASED TO $55K,
 HOWEVER THIS VALUE IS WAY LOW. PLEASE
 KNOW, IF THIS IS NOT ADJUSTED
 APPROPRIATLY, ONE WILL BE ASSESSED BASED
 ON THE MARSHALLS & SWIFT GUIDE AND
 TODAYS CURRENT RATES ADOPTED INTO TEH
 FBC. 108.3.
 THE VALUE ON THE GENERATO ALONE IS
 HIGHER THAN THAT GIVEN, WHICH DOES NOT
 INCLUDE THE $10K+ ATS, , SLAB, AND
 LABOUR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL BE
 INLCUDED. PLEASE KNOW, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3 , ADMIN SECT.
 PLEASE ADJUSTOR ONE WILL BE ASSESSED
 PER MARSHALL'S SWIFT GUIDE AS ADOPTED
 UNDER THE FBC.
  
 2) NOTE: SUBMITTED, HOWEVER THIS WILL BE
 REVIEWED BY BUILDING. PLEASE SEE THAT
 THE ELEVATIONS FOR THIS MUST BE A MINOF
 6" ABOVE BFE. THIS IS NOT YET INDICATED
 ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SLAB INFORMATION
 AT THIS TIME. PLEASE KNOW, THE SIZE, TIE
 DOWN ETC FOR GEN AND SLAB INFORMATION IS
 REQUIRED AT THIS TIME BEFORE PERMIT FOR
 GENERATOR CAN BE ISSUED.
 PLEASE SEE BUIDLING REVIEW COMMENTS.
 106.1.2
  
 3) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE AND CLARIFY
 ATS BEING INSTALLED. NO
 SPES/MANUFCATURES CUT SHEETS WERE
 SUBMITTED FOR REVIEW. PLEASE SEE A PRINT
 OUT FROM AN WEBSITE INDICATE AN "ONAN"
 YET PLANS CALL FOR GENERAC ATS WHICH
 WOULD CORRELATE WITH THE LISTED GENERAC
 GENERATOR.
 PLEASE CORRELATE AND SUBMIT ALL
 INFORMATION.
 PLEASE SEE MISSING WP HOUSING SPECS.
 PLEASE BE SURE MIN CLEARENCES ARE
 INDICATE FOR GEN AND PLEASE BE SURE AIC
 RATINGS FOR ALL EQUIPMENT IS SHOWN.
 110.9,702.6,215.5,110.26,110.3,90.7 ETC
  
 4) NOTE: NO, SEEMS TO BE SUBMITTED,
 HOWEVER LISTINGS TO BE VERIFIED.
 PLEASE SEE NO CALCULATIONS WERE
 SUBMITTED FOR FUEL USESAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPECS/CUT
 SHEET FOR FUEL TANK AND SIZE. PLEASE
 INDICATE GPH USESAGE AND SHOW ON PLANS.
 PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT
 WILL BE SEPARATE THIS INFORMATION IS
 REQUIRED AT THIS TIME. PLEASE ALSO SEE
 MECH REVIEW AND FIRE REVIEW COMMENTS.
 110.3,90.7,
 106.1.2 FBC
  
 5) NOTE: NO, SAME NOTE>
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE NFPA-110
 PLEASE SEE CHAPTER 27 OF THE 2004 FBC,
 AND 2002 110.
  
 6) NOTE: NO, THIS WAS DONE, HOWEVER THIS
 INFORMATION WAS HANDWRITTEN ON PLANS
 WHICH IS NOT PERMITTED. PLEASE BES URE
 THE ENGINEER OF RECORD MAKES THE
 REQUIRED CHANGES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW AND INDICATE ALL
 SETBACKS FOR GENERATOR AND EQUIPMENT.
 106.1.2
  
 7) NOTE:NO, SAME NOTE. NOT ENNOUGH
 INFORMATION SUBMITTED FOR COMPLETE
 REVIEW AND CODE COMPLIANCE IS NOT YET
 MET.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THE EXISTING
 MAIN PANEL WHERE IT APPEARS TO BE
 LOCATED ADJACENT TO THE NEW SE RATED ATS
 CONTAINS A MAIN?
 PLEASE ALSO PROVIDE INFORMATION BY THE
 WAY OF THE SPECS TO BE SUBMITTED AND
 PLANS THAT THE ATS CONTAINS A MANUAL
 MEANS OF DISCONNECT RATED FOR THE LOAD
 SERVED ON THE OUTSIDE AS REQUIRED PER
 230.70,230.76,230.79.
 PLEASE KNOW, IF THE EXISTING MAIN PANEL
 DOES NOT CONTAIN MCB, AND THE ATS DOES
 NOT DISCONNECT POWER FROM BOTH NORMAL
 AND EM SIDES TO A CENTER OFF POSITION, A
 MEANS OF DISCONNECT WILL BE REQUIRED
 LOCATED AT BUIDLING GROUPED WITH OUTHER
 MAINS.
 225.31-225.39, 230.72, 230.70
  
  
 ** NEW NOTRES**
  
 8) NOTE: PLEASE SEE ONLY ONE SET OF
 PLANS ARE SIGNED, DATED AND SEALED.
 PLEASE SEE FAC 61G15-23.002, FS 471.025.
  
 9) NOTE: PLEASE SEE AS THE SAME PLANS
 ORIGINAL SUBMITTED WERE BROUGHT BACK
 WITH HAND DRAWN CHANGES ON SOME SHEETS,
 AND NOT CORRECTIONS MADE, ONE SET OF
 PLANS ARE BEING RETAINED FOR FILE FOR
 POSSIBLE REVIEW BY THE FBPE'S.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT
 TO REPEAT CODE COMPLIANT COMMENTS FOR
 DESIGN PREOFESSIONALS.
  
 10) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT SUBMITTED IS NO LONGER VALID
 AND IS NULL AND VOID. PLEASE SEE FS
 713.13(2). WHEN WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING SUCH NOC,
 THEN THE DOCUMENT OF VOID>
 ** THE RECORDED NOC IS ONLY REQUIRED
 WHEN PICKING UP PERMIT.
  
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL AND OTHER
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717