2006-08-21 00:00:00DENIED:DIESEL GENRATOR
 ELECTICAL PERMIT 06061709
  
 1.PLEASE PROVIDE INFORMATION ON THE
 GENERATOR'S FUEL TANK, I.E. SUB-BASE,
 ABOVE GROUND, UNDERGROUND, CAPACITY,
 ETC.
  
 2.PROVIDE INFORMATION FOR THE FUEL
 PIPING, SIZE, MATERIAL, LAYOUT, SUPPORT,
 ETC.
  
 3.INDICATE DISTANCES/CLEARANCES FROM
 THE GENERATOR TO PROPERTY LINES,
 BUILDINGS, FRESH AIR INTAKES, WINDOWS,
 DOORS, LOUVERS, ETC.SHOW COMPLIANCE
 WITH 2004 FMC 401.5, 401.5.1 & 501.2.
  
 4.ADDITIONAL PERMIT FOR THE FUEL OIL
 STORAGE, IF THIS IS NOT A SUB-BASE FUEL
 TANK.PLEASE NOTE, ABOVE GROUND &
 UNDERGROUND TANKS WITH THE CAPACITY
 GREATER THAN 500 GALLON SHALL BE
 SUBMITTED TO DERM TO THE ATTENTION OF
 CHIP GREEN.PLANS MAY BE SUBMITTED AT
 3323 BELVEDERE RD., BUILD # 502.
  
 5.PLEASE PROVIDE ANCHORING DETAIL.
  
 6.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL OF THE "PRECAST CONTRETE
 BASE".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719
 OR E-MAIL [email protected].
  