Plan Review Notes
Plan Review Notes For Permit 06061708
Permit Number 06061708
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-21 00:00:00******** UNSAT ************
  
 1) NOTE: PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL BE
 INLCUDED. PLEASE KNOW, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3 , ADMIN SECT.
 PLEASE ADJUSTOR ONE WILL BE ASSESSED
 PER MARSHALL'S SWIFT GUIDE AS ADOPTED
 UNDER THE FBC.
  
 2) NOTE: PLEASE PROVIDE SLAB INFORMATION
 AT THIS TIME. PLEASE KNOW, THE SIZE, TIE
 DOWN ETC FOR GEN AND SLAB INFORMATION IS
 REQUIRED AT THIS TIME BEFORE PERMIT FOR
 GENERATOR CAN BE ISSUED.
 PLEASE SEE BUIDLING REVIEW COMMENTS.
 106.1.2
  
 3) NOTE: PLEASE CORRELATE AND CLARIFY
 ATS BEING INSTALLED. NO
 SPES/MANUFCATURES CUT SHEETS WERE
 SUBMITTED FOR REVIEW. PLEASE SEE A PRINT
 OUT FROM AN WEBSITE INDICATE AN "ONAN"
 YET PLANS CALL FOR GENERAC ATS WHICH
 WOULD CORRELATE WITH THE LISTED GENERAC
 GENERATOR.
 PLEASE CORRELATE AND SUBMIT ALL
 INFORMATION.
 PLEASE SEE MISSING WP HOUSING SPECS.
 PLEASE BE SURE MIN CLEARENCES ARE
 INDICATE FOR GEN AND PLEASE BE SURE AIC
 RATINGS FOR ALL EQUIPMENT IS SHOWN.
 110.9,702.6,215.5,110.26,110.3,90.7 ETC
  
 4) NOTE: PLEASE SUBMIT THE SPECS/CUT
 SHEET FOR FUEL TANK AND SIZE. PLEASE
 INDICATE GPH USEGAE AND SHOW ON PLANS.
 PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT
 WILL BE SEPARATE THIS INFORMATION IS
 REQUIRED AT THIS TIME. PLEASE ALSO SEE
 MECH REVIEW AND FIRE REVIEW COMMENTS.
 110.3,90.7,
 106.1.2 FBC
  
 5) NOTE: PLEASE SPECIFY THE NFPA-110
 PLEASE SEE CHAPTER 27 OF THE 2004 FBC,
 AND 2002 110.
  
 6) NOTE: PLEASE SHOW AND INDICATE ALL
 SETBACKS FOR GENERATOR AND EQUIPMENT.
 106.1.2
  
 7) NOTE: PLEASE CLARIFY IF THE EXISTING
 MAIN PANEL WHERE IT APPEARS TO BE
 LOCATED ADJACENT TO THE NEW SE RATED ATS
 CONTAINS A MAIN?
 PLEASE ALSO PROVIDE INFORMATION BY THE
 WAY OF THE SPECS TO BE SUBMITTED AND
 PLANS THAT THE ATS CONTAINS A MANUAL
 MENAS OF DISCONNECT RATED FOR THE LOAD
 SERVICED ON THE OUTSIDE AS REQUIRED PER
 230.70,230.76,230.79.
 PLEASE KNOW, IF THE EXISTING MAIN PANEL
 DOES NOT CONTAINA MCB, AND THE ATS DOES
 NOT DISCONNECT POWER FROM BOTH NORMAL
 AND EM SIDES TO A CENTER OFF POSITION, A
 MEANS OF DISCONNECT WILL BE REQUIRED
 LOCATED AT BUIDLING GROUPED WITH OUTHER
 MAINS.
 225.31-225.39
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL AND OTHER
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  