2006-07-21 00:00:00 | ******** UNSAT ************ |
| |
| 1) NOTE: PLEASE SEE THE VALUE FOR |
| COMPLETE SCOPE OF WORK SHALL BE |
| INLCUDED. PLEASE KNOW, EVEN IF ANY |
| EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3 , ADMIN SECT. |
| PLEASE ADJUSTOR ONE WILL BE ASSESSED |
| PER MARSHALL'S SWIFT GUIDE AS ADOPTED |
| UNDER THE FBC. |
| |
| 2) NOTE: PLEASE PROVIDE SLAB INFORMATION |
| AT THIS TIME. PLEASE KNOW, THE SIZE, TIE |
| DOWN ETC FOR GEN AND SLAB INFORMATION IS |
| REQUIRED AT THIS TIME BEFORE PERMIT FOR |
| GENERATOR CAN BE ISSUED. |
| PLEASE SEE BUIDLING REVIEW COMMENTS. |
| 106.1.2 |
| |
| 3) NOTE: PLEASE CORRELATE AND CLARIFY |
| ATS BEING INSTALLED. NO |
| SPES/MANUFCATURES CUT SHEETS WERE |
| SUBMITTED FOR REVIEW. PLEASE SEE A PRINT |
| OUT FROM AN WEBSITE INDICATE AN "ONAN" |
| YET PLANS CALL FOR GENERAC ATS WHICH |
| WOULD CORRELATE WITH THE LISTED GENERAC |
| GENERATOR. |
| PLEASE CORRELATE AND SUBMIT ALL |
| INFORMATION. |
| PLEASE SEE MISSING WP HOUSING SPECS. |
| PLEASE BE SURE MIN CLEARENCES ARE |
| INDICATE FOR GEN AND PLEASE BE SURE AIC |
| RATINGS FOR ALL EQUIPMENT IS SHOWN. |
| 110.9,702.6,215.5,110.26,110.3,90.7 ETC |
| |
| 4) NOTE: PLEASE SUBMIT THE SPECS/CUT |
| SHEET FOR FUEL TANK AND SIZE. PLEASE |
| INDICATE GPH USEGAE AND SHOW ON PLANS. |
| PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT |
| WILL BE SEPARATE THIS INFORMATION IS |
| REQUIRED AT THIS TIME. PLEASE ALSO SEE |
| MECH REVIEW AND FIRE REVIEW COMMENTS. |
| 110.3,90.7, |
| 106.1.2 FBC |
| |
| 5) NOTE: PLEASE SPECIFY THE NFPA-110 |
| PLEASE SEE CHAPTER 27 OF THE 2004 FBC, |
| AND 2002 110. |
| |
| 6) NOTE: PLEASE SHOW AND INDICATE ALL |
| SETBACKS FOR GENERATOR AND EQUIPMENT. |
| 106.1.2 |
| |
| 7) NOTE: PLEASE CLARIFY IF THE EXISTING |
| MAIN PANEL WHERE IT APPEARS TO BE |
| LOCATED ADJACENT TO THE NEW SE RATED ATS |
| CONTAINS A MAIN? |
| PLEASE ALSO PROVIDE INFORMATION BY THE |
| WAY OF THE SPECS TO BE SUBMITTED AND |
| PLANS THAT THE ATS CONTAINS A MANUAL |
| MENAS OF DISCONNECT RATED FOR THE LOAD |
| SERVICED ON THE OUTSIDE AS REQUIRED PER |
| 230.70,230.76,230.79. |
| PLEASE KNOW, IF THE EXISTING MAIN PANEL |
| DOES NOT CONTAINA MCB, AND THE ATS DOES |
| NOT DISCONNECT POWER FROM BOTH NORMAL |
| AND EM SIDES TO A CENTER OFF POSITION, A |
| MEANS OF DISCONNECT WILL BE REQUIRED |
| LOCATED AT BUIDLING GROUPED WITH OUTHER |
| MAINS. |
| 225.31-225.39 |
| |
| PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL AND OTHER |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |