2006-08-10 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06061708 |
| ADD: 3200 N MILITARY TRL |
| CONT: CONTACT ELEC |
| TEL: (561)620-0812 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) LOCATION FLOOD ZONE : A-8 FLOODZONE |
| MINIMUM TOP ELEVATION OF SLAB IS 16.5'. |
| PANEL# 120229 0015 B |
| PROVIDE FLOOD ZONE ELEVATION |
| CERTIFICATE FOR NEW CONSTRUTION WITH |
| BASE FLOOD ELEVATION, WILL BE REQUIRED |
| BEFORE A CERTIFICATE OF COMPLETION WILL |
| BE ISSUED. |
| |
| 3) PLANS INDICATE SLAB BY OTHERS, WHO? |
| A PERMIT IS REQUIRED. |
| GENERATOR SLAB & ANCHOR REQUIREMENT |
| PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| PLUS PROVIDE PLANS WITH THE INFORMATION |
| DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| FASTENER, AND THE MINIMUM EDGE DISTANCE |
| THE DEVICE REQUIRES WITHOUT LOAD |
| REDUCTION. |
| SECOND, PROVIDE INFORMATION ON THE |
| SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| WIREMESH, FIBER MESH OR IF STEEL REBAR |
| WILL BEUSED. |
| THE NEW SLAB AND HOLD DOWN DETAILS: |
| 104.2.1* ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |