2006-07-15 00:00:00 | |
| DENIED |
| |
| 1) AUTHORIZATION LETTER FROM A ENGINEER |
| SHALL BE SIGNED, SEALED AND DATED |
| |
| 2) SITE DRAWING DOES NOT CONTAIN THE |
| WIND LOAD DESIGN DATA PER 1603.1.4 FBC |
| |
| 3) DUE TO THE BOARD OF ENGINEERS RECENT |
| CONCERNS WITH THE DESIGN OF SCEEN |
| ENCLOSURES AND THIS PRESCRIPTIVE GUIDE |
| PLEASE SUBMIT ENGINEERED, SIGNED, SEALED |
| AND DATED SHEETS FOR THE CONSTRUCTION OF |
| SCREEN ENCLOSURES. THIS REQUIREMENT IS |
| PROVIDED FOR UNDER 2002.1 FBC |
| |
| 4) THE REVIEW OF PAGES OF INFORMATION |
| THAT ARE NOT CLEARLY MARKED AS TO THE |
| STRUCTURAL COMPONENTS BEING USED EXTENDS |
| REVIEW TIME. ALSO BE AWARE THAT THE AAF |
| GUIDE WAS NOT CORRECTLY FOLLOWED AS THE |
| SPAN IN THE SITE SPECIFIC DRAWING IS |
| GREATER THAN THE CHOSEN MEMBER IS |
| ALLOWED TO SPAN IN THEGUIDE PAGES |
| SUBMITTED.(BOTH BEAMS AND COLUMNS) |
| |
| 5) SITE DRAWING DOES NOT SPECIFY TYPE OF |
| 2X9 BEAM THAT IS TO BE USED ALTHOUGH |
| NEITHER WILL WORK FOR SPECIFIED SPAN |
| |
| 6) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO A |
| PERMIT BEING ISSUED |
| |