2006-07-03 00:00:00*** NOTES **
  
 ELECTRICAL PLANS STAMPED WITH THE
 FOLLOWING REDLINED.
  
 1)PLEASE SEE 210.52A5 FOR MIN OF 10FT
 GRND ROD REQUIRED.
 2) PLEASE SEE PANEL SCHEDULE SHOWS
 JACUZZI GFI, YET PLANS DO NOT SHOW ANY
 ELECTRICAL FOR THIS??
 3) PLEASE SEE NOTE ON PLANS MENTIONS ARC
 FAULT REQUIRED FOR RECEPTS ONLY AS THIS
 PROTECTION IS REQUIRED FOR ALL
 "OUTLETS", SD'S, LTS, FANS ETC.
  
  
  
 ** IMPORTANT**
  
 SIGNATURE ON APPLICATION FOR ROOFING
 CONTRACTOR IS NOT ORIG.NOTE ATTACHED TO
 PERMIT APPL.