2006-12-13 11:18:40 | | | BUILDING PLAN REVIEW | | PERMIT: 06061595 | | ADD: 422 SUNSET | | CONT: BURKHARDT CONSTRUCTION | | TEL: (561)718-2602 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | PLANS INDICATE THAT EYE-HOOKS ARE TO BE EMBEDDED INTO | | THE CONCRETE POUR WITH STRAPPING OVER THE GENERATOR? | | 106.1.2* ADDITIONAL INFORMATION REQUIRED: | | | | 1A) PLANS ARE TO IDENTIFY THE SIZE OF THE EYE-HOOK | | DIA.X LENGTH. | | 1B) WILL THERE BE A NUT AND WASHER AS PART OF THE | | EMBEDMENT? | | 1C) TYPE OF MATERIAL EYE-HOOK TO BE MADE OF? CARBON | | STEEL, GALVANINIZED? | | 1D) PLACEMENT OF EYE-HOOKS?VERSES STRAPS, PLEASE | | PROVIDE THE PLACEMENT OF BOTH THE BOLT EMBEDMENT AND | | STRAPS SINCE THE STRAPS CAN NOT BLOCK THE DOORS TO THE | | UNIT. | | 1E) PROVIDE ADDITIONAL INFORMATION ON THE TYPE OF | | MATERIAL TO BE USSED FOR THE STRAPS? | | 1F) WITH STRAP TYPE OF HOLD-DOWN AND TYPE OF MATERIAL | | STRAP IS TO BE MADE FROM, HOW MUCH PRESSURE IS TO BE | | REQUIRED TO HOLD THE GENERATOR IN PLACE WITHOUT | | SLIPPAGE OR MOMMENT | | OF OVERTURNING. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|