Plan Review Notes
Plan Review Notes For Permit 06061595
Permit Number 06061595
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-15 00:00:00****** UNSAT *********
  
 ** PLEASE SEE NOTES UNDER THE TWO
 PERMITS FOR REMODEL, AS THEY WILL AFFECT
 THIS PERMIT, SERVICE RISER ETC.
 PLEASE SEE SERVICE.
  
  
 1) NOTE: PLEASE SEE TYPE OF GENERATOR IS
 UNCLEAR AT THIS TIME. PLEASE SEE PERMIT
 APPLICATION HAS A MECHANCICAL CONTRACTOR
 SIGNED ON FOR A "FUEL PERMIT" WHICH
 LENDS TO THIS GEN BEING DIESEL, HOWEVER
 NO INFORMATION ON PLANS. PLEASE SEE NO
 SPECS ARE SUBMITTED FOR FUEL TANK ETC.
 PLEASE SEE PARTIAL "SITE PLAN" MENTIONS
 400 GAL TANK, BUT DOES NOT SPECIFY TYPE
 OF FUEL.
 PLEASE SEE COMMENTS FROM FIRE AND
 MECHANICAL REVIEW.
 PLEASE SUBMIT SPECS.
 106.1.2 FBC ADMIN SECT.
  
 2) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE GEN, ATS'S ETC.
 PLEASE KNOW, ALL SHALL INDICATE LISTINGS
 FROM A NRTL.
 110.3,702.6 ETC.
  
 3) NOTE: PLEASE SEE THAT PLANS SPECIFY
 FUEL CONSUMPTION. GPH ETC.
 PLEASE KNOW, AS PERMIT FOR GENERATOR IS
 BEING SUBMITTED UNDER 433 AVON RD, WHICH
 IS A SEPARATE LEGAL PCN ETC AND IF GEN
 IS FEEDING AND LEGALLY REQUIRED STAND-BY
 DEVICES ON 422 SUNSET RD, IT MAY BE
 DETERMINED THAT A UNITY OF TITLE MAY BE
 REQUIRED IF NOT ONE ALREADY.
 THIS WILL REQUIRE FURTHER CONSULTATION.
  
 4) NOTE: PLEASE CLARIFY IF THE GEN
 ENCLOSURE WILL REMAIN LOCKED, AS ACCESS
 TO SERVICE MEANS OF DISCONNECT SHALL BE
 READILY ACCESSIBLE.
 100, 230.70
  
  
 5) NOTE: PLEASE KNOW, THE NOC SUBMITTED
 WHICH MENTIONS "SITE-WORK" DOES NOT
 COVER THE INSTALLATION OF THE EM GEN
 ETC.
 PLEASE SEE KNOW, THAT A RECORDED NOC
 INCLUDING THE INSTALLATION OF THE GEN
 SHALL BE REQUIRED BEFORE PICKING UP
 PERMIT.
 FS 713.13
  
 6) NOTE: PLEASE INDICATE ALL EQUIPMENT
 ON "PARTIAL SITE PLAN" AS CLEARNECE OF
 ALL SERVICE EQUIPMENTNEEDS TO BE
 VERIFIED.110.26
  
 ** PLEASE KNOW, DUE TO POSSIBLE CHANGES
 IN SERVICE RISER, AND SOME INFORMATION
 NOT SUBMITTED THERE MAY BE COMMENTS ON
 FURTHER REVIEWS WHICH ARE NOT MENTIONED
 ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  