Plan Review Notes
Plan Review Notes For Permit 06061547
Permit Number 06061547
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-03 00:00:00***UNSAT ***
  
 ** PERMIT HAS BEEN TEMPORARYLIY PLACE ON
 "HOLD".
  
 1) NOTE: PLEASE KNOW PLANS ARE TO BE
 REVISED INDICATING THE NEW SERVICE
 DISONNECT CONTAINGIN OCP.
 PLEASE SEE FEEDERS NOW SHALL CONTAIN
 EQUIPMENT GROUNDING CONDUCTORS.
 PLEASE SEE MANUFACTURE'S SPEC/CUT SHEETS
 FOR THE MTS SHALL BE SUBMITTED (AN ATS
 IS ON FILE ).
 PLEASE SEE GROUNDING ELECTRODE SYSTEM
 FOR NEW SERVICE SHALL BE VERIFIED AND
 REVISED FOR MIN OHM'S.
 PLEASE SEE SITE LOCATION OF SERVICE MAY
 NOT PERMITTED AS THIS SEEMS TO BE A
 LEGAL EASEMENT FOR FPL. SHALL CONTAIN
 ALL LEGAL DOCUMENTION FOR EASMENT
 RELEASE FROM FPL, OT MOVE SERVICE
 LOCATION.
 RISER SEEMS TO SHOW LINE AND LOADS IN
 THE SAME GUTTER. THIS IS BEING REVISED.
  
 250.50,250.56, 215.5,250.122,250.6,
 250.24B,230.7,230.70,240.4,310.16
 90.8,110.3 ETC
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  