Plan Review Notes
Plan Review Notes For Permit 06061475
Permit Number 06061475
Review Stop E
Sequence Number 5
Notes
Date Text
2007-05-08 17:12:34** UNSAT **
  
 1) NOTE: PLEASE SEE REVIEW NOTES FROM PREVIOUS REVIEW
 AND NOTES AS REDLINED ON PROVISO AS NOTED ON PLANS
 ISSUED FOR PERMIT.
 PLEASE SEE THE TEXT BELOW WHICH WAS SENT TO THE
 ENGINEER VIA E-MAIL.
  
  
  
 MR. STEWART,
  
 UPON REVIEWING THE LOCATIONS OF THE TWO DISCONNECTS ON
 PLANS. THE LOCATIONS ARE TOO FAR APART AND CAN NOT BE
 ACCEPTED.
 PLEASE SEETHAT A DISCONNECT WOULD BE REQUIRED AT A
 LOCATION CLOSER AND IN CLOSE PROXIMITY OF THE EXISTING
 DISCONNECT FOR THIS BUILDING. THIS IS WHAT WAS REDLINED
 AS A "PROVISO" ON ORIGINAL PLANS. WHEN WE SPOKE ON THE
 PHONE I DID NOT HAVE THE PLANS, AND CAN NOW SEE HOW FAR
 THESE DISCONNECTS ACTUALLY ARE. MY DECISIONS IS THE
 SAME AS ON ORIGINAL REDLINED PLANS AND REVIEW UNDER THE
 PERMIT THAT THESE ARE TOO FAR APART.
 I CAN NOT ACCEPT THE SIGNAGE IN LIEU OF GROUPING THE
 DISCONNECTS FOR THIS BUILDING.
 MY NOTES AS STATED PREVIOUSLY WITH RESPECT TO MEETING
 EXCEPTION STILL WOULD STAND IF THAT METHOD/OPTION IT
 TAKEN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.